Full Product Manual
Rover Protections
Protection Behavior
When PV  shot  circuit occurs,  the controller  will  stop  charging. 
Clear it to resume normal operation.
If  the  PV  voltage  is  larger  than  maximum  input  open  voltage 
100VDC,  PV  will  remain  disconnected  until  the  voltage  drops 
below 100VDC.  
The  controller will  limit  the  battery  charging current  to  the 
maximum battery current rating. Therefore, an over-sized solar 
array will not operate at peak power.  
If  the  current  exceeds  the  maximum  load  current  rating  1.05 
times, the controller will disconnect the load. Overloading must 
be cleared up by reducing the load and restarting the controller.  
If the temperature of the controller heat sink exceeds 65℃, the 
controller  will  automatically  start  the  reducing  the  charging 
current and shut down when temperature exceeds 80℃.  
The controller will not operate if the PV wires are switched. Wire 
t
hem correctly to resume normal controller operation.  
The controller will not operate if the battery wires are switched. Wire 
them correctly to resume normal controller operation. 
Fully  protected  against  the  load  wiring  short-circuit.  Once  the 
load  short  (more  than  quadruple  rate  current),  the  load  short 
protection  will  start  automatically.  After  5  automatic  load 
reconnect attempts, the faults must be cleared by restarting the 
controller.  
Over-Temperature
Battery Reverse Polarity
PV Reverse Polarity
Load Short Circuit
Load Overload
PV Overcurrent
PV Overvoltage
PV Array Short Circuit