Full Product Manual

26
System StatusTroubleshooting
PV indicator Troubleshoot
BATT Indicator Troubleshoot
Error Indicator Troubleshoot
Buzzer (Alarm) Troubleshoot
Off during daylight
Using a multimeter check the battery voltage and verify it is not
exceeding 68V volts.
Disconnect loads, if any, and let the PV modules charge the battery bank.
Use a multi-meter to frequently check on any change in battery voltage to
see if condition improves. This should ensure a fast charge. Otherwise,
monitor the system and check to see if system improves.
System Error. Please check LCD for Error code
Check the following, Battery under-voltage alert
White Slow Flashing
White Fast Flashing
White Solid
Buzzer on for 1 minute
Buzzing for 15 seconds
Buzzing continuously
Check the following, Battery over-discharged, Controller over-
temperature or Cattery over-temperature
Check the following, Battery over-voltage, PV reverse polarity,
PV over-voltage
Ensure that the PV wires are correctly and tightly secured inside the
charge controller PV terminals. Use a multi-meter to make sure the
poles are correctly connected to the charge controller.