Maintenance
For best controller performance, it is recommended that these tasks be performed from time to
time.
1. Check that controller is mounted in a clean, dry, and ventilated area.
2. Check wiring going into the charge controller and make sure there is no wire damage or
wear.
3. Tighten all terminals and inspect any loose, broken, or burnt up connections
Fusing
Fusing is a recommendation in PV systems to provide a safety measure for connections going
from panel to controller and controller to battery. Remember to always use the recommended
wire gauge size based on the PV system and the controller.
NEC Maximum Current for different Copper Wire Sizes
AWG
16
14
12
10
8
6
4
2
0
Max.
Current
10A
15A
20A
30A
55A
75A
95A
130A
170A
Fuse from Controller to Battery
Controller to Battery Fuse = Current Rating of Charge Controller
Ex. Adventurer = 30A fuse from Controller to Battery
Fuse from Solar Panel(s) to Controller
Ex. 200W; 2 X 100 W panels
Parallel
Total Amperage = I
sc1
+ I
sc2
= (5.75A + 5.75A) * 1.56
Fuse = minimum of 11.5 * 1.56 = 17.94 = 18A fuse