Full Product Manual
15
Parameters for commencing Equalization Charging,
Boost Charging, and Float Charging.
Parameters for Boost Voltage Reconnect, Boost
Under-Voltage Reconnect, and Boost Under-Voltage
warning.
Parameters for controller Low Voltage-Reconnect,
Low Voltage-Disconnect, and the Discharge Limit.
Parameter for setting a time duration for when the
controller approaches Equalization Charging and
Boost Charging.
4. Load Set
Use to cycle through the screens. Press to select
A load selection menu allows the user to control the
load terminal activation automatically, manually, or
with a timer.
This function will set the controller to manual mode by
default so the user is able to control when to turn the
load on or off.
NOTE: The user will need to set delay time to “0” so
that manual mode can be instant as opposed to waiting
for the delay time to pass.
Parameter Set
Equal Chrg: 14.6V
Boost Chrg: 14.4V
Float Chrg: 13.8V
Manual Default
>ON OFF
Manual
Light On/Off
Light On+Timer
Timer
ENTER/
/ -
/
Parameter Set
Boost V. Rect: 13.2 V
Under V. Rect: 12.2 V
Under V. Warn: 12.0 V
Parameter Set
Low V. Rect: 12.6V
Low V. Disc: 11.1V
Discharg Lmt: 10.6V
Parameter Set
Equa. Time: 120Min
Boost Time: 120Min