User Manual
28
Parameters Number
Parameter Name Description
Set options
The range can be configured
between 0-40A
Supply for industrial frequency
transformer (disabled)
Supply for industrial frequency
transformer (enabled)
[28] 40A
(Default)
[29] DIS
(Default)
[29] ENA
28
29
Maximum AC
Charging Current
Split Phase
No alarm
Enable alarm
25
[25] DIS
Buzzer alarm
[25] ENA
(Default)
No alarm prompts when the status
of the primary input source
changes
Enable alarm prompts when the
status of the primary input source
changes
26
[26] DIS
Alarm
[26] ENA
(Default)
When disabled, the unit will not
transfer to Utility mode
When enabled, the unit will
transfer to Utility mode if overload
occurs in battery mode.
[27] DIS
[27] ENA
(Default)
27
Overload bypass:
When enabled,
the unit will
transfer to line
mode if overload
occurs in battery
mode.
35
[35] 50.4V
(Default)
Set point that recovers and
reconnects the solar inverter from
being disconnected in Low
Voltage Disconnect. The range is
from 44V -58.4V, in 0.4V
increments.
Low Voltage
Disconnect
Recover
36
[36] 80A
(Default)
Adjustable PV current settings.
The range is from 0 – 80A.
PV Charging
Current
37
[37] 52V
(Default)
When the battery reached at
floating status, it will need to be
lower than this setpoint before it
starts charging. The range is the
( Undervoltage Warning )~
( Floating Voltage – 1.2V )for
the respective battery
Battery Charging
Boost Return
Setpoint