(d) Processing of overflow if capture trigger interval is long
If the pulse width is greater than one cycle of the 16-bit counter, care must be exercised because an overflow
may occur more than once from the first capture trigger to the next. First, an example of incorrect processing is
shown below.
Example of incorrect processing when capture trigger interval is long
FFFFH
16-bit counter
0000H
TPnCE bit
TIPnm pin input
TPnCCRm register
INTTPnOV signal
TPnOVF bit
Dm0 Dm1
Dm0
Dm1
<1> <2> <3> <4>
1 cycle of 16-bit counter
Pulse width
The following problem may occur when long pulse width is measured in the free-running timer mode.
<1> Read the TPnCCRm register (setting of the default value of the TIPnm pin input).
<2> An overflow occurs. Nothing is done by software.
<3> An overflow occurs a second time. Nothing is done by software.
<4> Read the TPnCCRm register.
Read the overflow flag. If the overflow flag is 1, clear it to 0.
Because the overflow flag is 1, the pulse width can be calculated by (10000H + D
m1 Dm0)
(incorrect).
Actually, the pulse width must be (20000H + D
m1 Dm0) because an overflow occurs twice.
If an overflow occurs twice or more when the capture trigger interval is long, the correct pulse width may not be
obtained.
If the capture trigger interval is long, slow the count clock to lengthen one cycle of the 16-bit counter, or use
software. An example of how to use software is shown next.