Datasheet
RL78/L12 CHAPTER 22 VOLTAGE DETECTOR 
R01UH0330EJ0200 Rev.2.00      764 
Dec 13, 2013 
Table 22-1. LVD Operation Mode and Detection Voltage Settings for User Option Byte (000C1H) (2/2) 
Address: 000C1H 
  7 6 5 4 3 2 1 0 
 VPOC2 VPOC1 VPOC0 1 LVIS1 LVIS0 LVIMDS1 LVIMDS0
• LVD setting (interrupt mode) 
Detection voltage  Option byte setting value 
VLVD VPOC2 VPOC1 VPOC0 LVIS1 LVIS0 Mode setting 
Rising edge  Falling edge  LVIMDS1 LVIMDS0
1.67 V 1.63 V 0 0 0 1 1 0 1 
1.77 V  1.73 V  0  0  1  0 
1.88 V  1.84 V  0  1  1  1 
1.98 V  1.94 V  0  1  1  0 
2.09 V  2.04 V  0  1  0  1 
2.50 V  2.45 V  1  0  1  1 
2.61 V  2.55 V  1  0  1  0 
2.71 V  2.65 V  1  0  0  1 
2.81 V  2.75 V  1  1  1  1 
2.92 V  2.86 V  1  1  1  0 
3.02 V  2.96 V  1  1  0  1 
3.13 V  3.06 V  0  1  0  0 
3.75 V  3.67 V  1  0  0  0 
4.06 V  3.98 V  1  1  0  0 
Other than above  Setting prohibited. 
• LVD off (use of external reset input via RESET pin) 
Detection voltage  Option byte setting value 
VLVD VPOC2 VPOC1 VPOC0 LVIS1 LVIS0 Mode setting 
Rising edge  Falling edge  LVIMDS1 LVIMDS0
−  − 
1 
×  ×  ×  × 
0/1 1 
Other than above  Setting prohibited. 
Cautions  1.  Be sure to set bit 4 to 1. 
  2.  After power is supplied, the reset state must be retained until the operating voltage becomes in 
the range defined in 30.4 or 31.4 AC Characteristics. This is done by utilizing the voltage 
detection circuit or controlling the externally input reset signal. After the power supply is turned 
off, this LSI should be placed in the STOP mode, or placed in the reset state by utilizing the 
voltage detection circuit or controlling the externally input reset signal, before the voltage falls 
below the operating range. The range of operating voltage varies with the setting of the user 
option byte (000C2H). 
Remarks 1.  ×: don’t care 
 2.  For details on the LVD circuit, see CHAPTER 22 VOLTAGE DETECTOR. 
  3.  The detection voltage is a TYP. value. For details, see 30.6.4 or 31.6.4 LVD circuit characteristics. 
<R> 










