Instruction manual
Underwriters Laboratories (UL) Compliance
Access Control Design Guide
55
Power-Limited Wiring
UL compliance requires power-limited and non-power-limited wiring to be separated by at least 0.25”
(7mm). Any additional power supply used (e.g. for door releases and auxiliary outputs) must be power
limited, UL Listed for Access Control Systems and Accessories. The recommended cable routing diagrams
in the cabinet installation instructions show power-limited and non-power limited wiring.
Strain Relief
All cables leaving the cabinet must be in conduit/trunking, or must employ a UL-listed strain relief device.
Minimum Requirements for Computer Accessory Equipment
The PC running the SMS software must be ITE UL Listed to UL 60950.
Please refer to the Software Installation Manual for details of the minimum hardware and software
requirements.
Transient Suppressors
Transient protection must meet or exceed the following UL standards for equipment safety:
• Communications circuits & network components; UL497A: Standard for Secondary Protectors for
Communications Circuits (UL274 27.2f).
• Signal Line Transients; UL497B: Standard for Protectors for Data Communications and Fire Alarm
Circuits, maximum rating of 50 volts (UL294 27.2e).
• Supply Line Transients; UL1449 Standard for Transient Voltage Surge Suppressors (UL294 27.2d).
Environmental
If the computer accessory equipment is to be installed in a temperature-controlled environment, 24 hours
of standby power supply must be provided for the Heating Ventilation and Control (HVAC) system, which
must maintain the environment between 55 and 95 degrees F (13-35 degrees C). The standby power
system for the HVAC system must be supplied by an engine-driven generator alone. A standby battery is
not required to be used (UL294 27.2g).
Emergency Egress and System Failure Mode
Locking mechanisms must be installed to allow fail-safe egress, such as during a total loss of main and
backup power. Consult the local Authority Having Jurisdiction (AHJ) when installing access control readers
and locking mechanisms to any portal in an egress path.
A system failure, such as loss of the system program, system lock-up or total failure, does not allow
unauthorized access, although a partial loss of operation may occur.