Specifications

32
ZWaveConfigurationParameters
Differentuserhasdifferentpreferre dsettingsoftheirthermostat,youmayusethebelowconfiguration
parameterstochangeset tingsofcorrespondingfunctionality.
Functions ParameterNumber Parametervaluerange
Swing 1(0x01) 1(0x01)=1
o
F/0.5
o
C
2(0x02)=2
o
F/1.0
o
C(default)
3(0x03)=3
o
F/1.5
o
C
4(0x04)=4
o
F/2.0
o
C
Differential 2(0x02) 1(0x01)=1
o
F/0.5
o
C
2(0x02)=2
o
F/1.0
o
C(default)
3(0x03)=3
o
F/1.5
o
C
4(0x04)=4
o
F/2.0
o
C
Setfiltercounter 3(0x03) 500(0x01F4)to4000(0x0FA0)hours
Default=500(0x01F4)hours
Resolution=100(0x0064)hours
Reportfiltercounter
(readonly)
4(0x04) 0(0x0000)to9999(0x270F)hours
Scaleoftemperature 5(0x05) 0(0x00)=
o
C
1(0x01)=
o
F(default)
Upperlimitofsetpoint(A) 6(0x06) (A)availablerange:
UnitinCelsius(
o
C):
A=(B+2)min.~(37.0
o
C)max.
UnitinFahrenheit(
o
F):
A=(B+4)min.~(99.0
o
F)max.
(default=99.0
o
F)
Lowerlimitofsetpoint(B) 7(0x07) (B)availablerange:
UnitinCelsius(
o
C):5.0
o
Cto35.0
o
C
UnitinFahrenheit(
o
F):41.0
o
Fto95.0
o
F
(default=41.0
o
F)
EasyMode 8(0x08) 0(0x00)=Disable
1(0x01)=Enable,default
Timeformat 9(0x09) 0(0x00)=24hours
1(0x01)=12hours(am/pm),default
Repeatbasicsetcounter
(AssociationGroupAandB
only)
10(0x0A) Value(X)
0(0x00),3(0x03)to255(0xFF)
0(0X00)=Disable,default
3(0x03)to255(0xFF)minutes
(Thermostatsends“BasicSet”
commandtoitsassociationnode
repeatedlyineveryXminutes)