User's Manual

28
Z-Wave Configuration Parameters
Different users have different preferred settings of their thermostat, you may use the below
configuration parameters to change settings of corresponding functionality.
The size of Parameter number is 1 byte; Parameter value can be 1, 2, or 4 bytes.
Functions Parameter Number
Parameter value range
Scale of temperature 1 (0x01) 0 (0x00) =
o
C
1 (0x01) =
o
F (default)
Swing 2 (0x02) 1 (0x01) = 1
o
F / 0.5
o
C
2 (0x02) = 2
o
F / 1.0
o
C (default)
3 (0x03) = 3
o
F / 1.5
o
C
4 (0x04) = 4
o
F / 2.0
o
C
Differential 3 (0x03) 1 (0x01) = 1
o
F / 0.5
o
C
2 (0x02) = 2
o
F / 1.0
o
C (default)
3 (0x03) = 3
o
F / 1.5
o
C
4 (0x04) = 4
o
F / 2.0
o
C
Dead band
(On thermostats that
automatically control both
heating and cooling systems, a
dead band is a temperature
range in which neither system
turns on. The dead band
prevents the thermostat from
activating heat and cooling in
rapid succession. This
conserves energy by providing
a range of temperatures
requiring no energy
consumption)
4(0x04)
Dead band value:
3(0x03)= 3
o
F/ 1.5
o
C
4(0x04)= 4
o
F/ 2.0
o
C (default)
5(0x05)= 5
o
F/ 2.5
o
C
6(0x06)= 6
o
F/ 3.0
o
C
Upper limit of Heat set point
(In order to save energy special
in motel service, advance user
or administrator can limit the
upper heat set point)
5 (0x05)
If in Heat
and Auto
mode:
=====================================
Unit in F:
Range from 41
o
F to (99
o
F - dead band)
Default = 95
o
F
Example 82
o
F; input = 820 (0x0334)
Unit in C:
Range from 5
o
C to (37
o
C – dead band)
Default = 35
o
C
E
xample 28
o
C; input = 280 (0x0118)
Lower limit of Cool set point
(In order to save energy special
6 (0x06)
If in Cool mode
and Auto Mode
:
=====================================
Unit in F:
Range from (41
o
F + dead band) to 99
o
F
Default = 45
o
F