Association Groups setting example (case 3):
Z-Wave Configuration Parameters
Different user has different preferred settings of their thermostat, you may use the
below configuration parameters to change settings of corresponding functionality.
500 (0x01F4) to 4000 (0x0FA0) hours
Default = 500 (0x01F4) hours
Resolution = 100 (0x0064) hours
3 (0x03)
Set filter counter
F-BW8041 (ZFM-80)
(Node ID-A)
F-BW8041 (ZFM-80)
(Node ID-B)
F-BW8041 (ZFM-80)
(Node ID-C)
F-BW8041 (ZFM-80)
(Node ID-D)
Z-Wave Gateway
(Node ID-E)
Association group_1
for Heat Pump
Association group_2
for Compressor
Association group_3
for Auto report to
gateway
F-BW8031 (ZTS-110)
Parameter value rangeParameter No.
o o
1 (0x01) = 1 F / 0.5 C
o o
2 (0x02) = 2 F / 1.0 C (default)
o o
3 (0x03) = 3 F / 1.5 C
o o
4 (0x04) = 4 F / 2.0 C
1 (0x01)
o o
1 (0x01) = 1 F / 0.5 C
o o
2 (0x02) = 2 F / 1.0 C (default)
o o
3 (0x03) = 3 F / 1.5 C
o o
4 (0x04) = 4 F / 2.0 C
2 (0x02)
Functions
Swing
Differential
Support Association Groups (Association Command Class)
ZTS-110 supports 3 association groups.
Association group_3: (Auto report)
- Association group_3 is used to report status change to gateway. (Only gateway
or controller can be assigned in this association group)
ZTS-110 will trigger AUTO report function if one of below status is changed.
I. Operation mode (Off, Heat, Cool, Auto)
II. Operation state (Heat on or off, Cool on or off)
III. Fan mode (Auto, Auto low)
IV. Fan state (Fan on or Fan off)
o
V. Heat set point (report in precision 1 after decimal, e.g. 21.1 C )
o
VI. Cool set point (report in precision 1 after decimal, e.g. 23.3 C )
o
VII. Current room temperature (report in precision 1 after decimal, e.g. 24.0 C)
o o
(It will trigger room temperature report if there is 4 F or 2 C (default) differ from
last report. You can change this setting by set the configuration parameter)
Note: Total 5 devices (nodes) can be assigned in total 3 association groups. Below
table lists out the devices (nodes) allocations in the 3 association groups.
Important: Please do not associate heat pump and compressor devices in same
association group because heat pump and compressor device cannot be turned on
simultaneously!
Case No.
No. of Node ID in
Association group_1
No. of Node ID in
Association group_2
No. of Node ID in
Association group_3
Case 1 4
0
1 (AUTO report)
Case 2
3
1
1 (AUTO report)
Case 3
2 2
1 (AUTO report)
Case 4
1
3
1 (AUTO report)
Case 5
0
4
1 (AUTO report)
Association group
Association group_1
(Heat pump)
Association group_2
(Compressor)
Mode
Heating mode
ON
(basic set command 0xFF)
OFF
(basic set command 0x00)
Cooling mode
OFF
OFF
(basic set command 0x00)
OFF
(basic set command 0x00)
ON
(basic set command 0xFF)
OFF
(basic set command 0x00)