Maximum heating circuit length (m) and definition of the circuit breaker (C- tripping characteristic)
Type Start-up
temperature °C
W/m
Operation voltage < AC 254 V
16 A 20 A 25 A 32 A
m m m m
MSB 10
07-5804-2...
+10
13
200 235 235 235
-25
175 235 235 235
-50
165 225 230 235
MSB 15
07-5804-2...
+10
19.5
165 189 189 189
-25
117 152 170 189
-50
110 144 160 189
MSB 25
07-5804-2...
+10
27.5
120 140 140 140
-25
88 120 130 140
-50
80 114 120 136
MSB 30
07-5804-2...
+10
34.5
85 114 114 114
-25
69 92 100 114
-50
65 86 92 110
MSB 40
07-5804-2...
+10
44
70 82 82 82
-25
49 66 75 82
-50
45 62 70 78
9. Type label heating system
The type label is to be filled in manually on the basis of the shown points.
The blanks in the heating system’s type number must be filled on the ba-
sis of the components used. A water-proof and lightfast marker must be
used (e. g.: Staedtler Lumocolor permanent special marker or BARTEC
no.: 02-7140-0001).
The serial number (connection and termination set) must and the TAG
number can be filled in by the person setting up the heating-circuit.
A practical example of a filled-in type label is given further on. The type
label must be stuck onto the lid of the junction box. The surface must
be cleaned first before the glue is applied. Care must be taken that the
sticker is put on carefully. It may not jut out over the correct area and it
may not have any air bubbles.