Operating instructions

21-1780-7D001/E-05/2013-BEH-D278563
EN 6/16
8. Heating circuit length
Maximum heating circuit length (m) and definition of the circuit breaker (C- tripping characteristic)
Type Start-up
temperature °C
W/m
Operation voltage < AC 120 V Operation voltage < AC 254 V
16 A 20 A 25 A 32 A 16 A 20 A 25 A 32 A
m m m m m m m m
HSB 10
07-5803-.10 A
+10
10
100 120 120 120 200 235 235 235
-15
89 120 120 120 175 235 235 235
-30
82 120 120 120 165 225 230 235
HSB 15
07-5803-.15 A
+10
15
80 95 95 95 165 189 189 189
-15
56 75 80 95 117 152 170 189
-30
52 75 80 95 110 144 160 189
HSB 25
07-5803-.25 A
+10
25
60 69 69 69 110 140 140 140
-15
44 59 64 69 88 120 130 140
-30
40 55 60 69 80 114 120 136
HSB 30
07-5803-.30 A
+10
30
44 58 58 58 85 114 114 114
-15
35 45 50 58 69 92 100 114
-30
32 41 45 58 65 86 92 110
HSB 45
07-5803-.45 A
+10
45
35 41 41 41 70 82 82 82
-15
24 33 35 41 49 66 75 82
-30
22 26 32 41 45 62 70 78
HSB 60
07-5803-.60 A
+10
60
25 32 32 32 50 64 64 64
-15
20 25 28 32 38 52 58 64
-30
17 21 26 32 35 48 52 60
HSB and MSB Operating instructions