Technical data
REMEHA QUINTA RANGE
7
Concentric room-sealed applications
Multiboiler with
low loss header
(open tube site
fabricated)
Typical flue systems
Quinta 30 Quinta 45 Quinta 65 Quinta 85 Quinta 115
80/125mm 80/125mm 100/150mm 100/150mm 100/150mm
max eq. length m 20 16 13 13 7
eq. length bend 45° m 1.2 1112
eq. length bend 90° m 4 2223
Calculation data – room-sealed applications
Quinta 30/45 Quinta 65/85 Quinta 115
No. of Boilers 2 3 4562345623 456
Low Loss Header Dia mm 100 125 150 150 200 150 200 225 250 250 150 200 250 250 300
Connecting Pipework “A” mm 42 42 50 50 50 50 65 80 80 100 50 65 80 100 100
Connecting Pipework “B” mm 50 50 65 80 80 65 80 100 125 125 80 100 125 125 125
Dimension "A" mm 300 375 450 450 600 450 600 675 750 750 450 600 750 750 900
Dimension "B" mm 350 425 500 500 650 500 650 725 800 800 500 650 800 800 950
VRS roof mounted
room-sealed
terminal
Quinta 65/85/115
100/150 System
Quinta 30/45
80/125 System
Based on 80°c/60°c Flow
Boiler side 20°ΔT/System Side 11°ΔT