Technical data

4
Operating principle
Combustion air is drawn into the closed air box, by a variable speed
fan, through the air inlet connection from the plant room (open flued)
or from outside via the concentric flue system (room-sealed). On the
inlet side of the fan is a specially designed venturi which is connected
to the outlet side of the gas combi block.
Depending on the demand (under the dictates of flow/return sensor
and other external/internal control inputs) the electronic control unit
directly monitors the volume of gas and air being delivered to the
premix burner. This mixture is initially ignited by the combined
ignition/ionisation probe which then monitors the state of the flame.
Should the flame not ignite or be unstable, within the pre-set safety
time cycle, the controls will shut the boiler down (after 5 attempts)
requiring manual intervention to reset the boiler. The digital display will
also indicate a flashing fault code confirming the reason for the failure.
Dimensions
Advantages
at a glance
High efficiency: 110% NCV at
40/30ºC (99% GCV)
Boiler control:
a) Modulating (18-100%)
b) High/low (18-100%)
c) On/off
Premix burner for
clean combustion
Low NO
x < 25ppm (02=0%, dry)
Quiet operation <48 dBA
Digital display
Data file for storing information
Remote signalling options
Cast aluminium heat exchanger
Easy maintenance
Built-in calorifier control
Options for modular control and/
or weather compensator
Control 0-10V signal or volt free
PC connection
Advanced boiler control, Remeha’s
‘abc’, for reliable heat delivery
Conventional or “room-
sealed” operation
Cascade packages for up to
6 boilers
Quick and easy installation
Space saving
For use with natural gas and L.P.G.
(Some models require a
conversion kit)
Flow connection 1
1
/
4
" BSP (m)
& 1" BSP (f)
Return connection 1
1
/
4
" BSP
(m) & 1" BSP (f)
Gas connection
3
/
4
" BSP (m)
Condensate connection
25 mm o/d (plastic)
Flue gas connection 80 mm
i/d (Quinta 45) and
100 i/d (Quinta 65/85/115)
Combustion air supply
connection 125mm (Quinta 45)
and 150 i/d (Quinta 65/85/115)
Holes for mounting bracket
Return connection ø 22 mm o/d
Second flow connection ø 22 mm o/d
(optional for DHW production with
3-way valve
Flow connection ø 22 mm o/d
Gas connection ø 15 mm o/d
Condensate connection 25 mm o/d
(plastic)
Combustion air supply connection
ø 125 mm i/d
Flue gas connection ø 80 mm i/d
Holes for mounting bracket
Air vent discharge
Quinta 30
Quinta 45/65/85/115
Dimension 'A'
Quinta 45 65 = 360
Quinta 85/115 = 452
'A'