Technical information
Remeha Quinta 30
38
If water treatment is used, we recommend the following products:
‘Copal
®
’ manufactured by: or: Sentinal ‘X100
®
’ manufactured by:
Fernox, Cookson Electronics BetzDearborn Ltd
Forsyth Road Sentinal
Sheerwater Foundry Lane
Woking Widnes
Surrey GU21 5RZ Cheshire WA8 8UD
Tel No: 01483 793200 Tel No: 0151 424 5351
Fax No: 01483 793201 Fax No: 0151 420 5447
Email: sales@fernox.com
Web site: www.fernox.com
For the correct dosage and for further information on water treatment or system clea-
ning we advise direct contact with either of the above companies.
7.4.3 Cold feed and expansion tank height for open vented systems
We recommend the boiler is installed on a closed (pressurised) system wherever pos-
sible with a minimum operating pressure of 0.8 bar. However, open vented systems
can be accomodated as follows: The cold feed and expansion tank heights for all open
vented systems must comply with the requirements laid down in the Health and Safety
Executive publication (latest execution).
The Remeha Quinta series boilers require a minimum static head of 3 m.
7.4.4 Safety valve
A safety valve should be fitted in accordance with the British Standards. Recommen-
ded minimum size of 15 mm (full bore type).
7.4.5 Gas connection
Connect the boiler to the incoming gas in accordance with the requirements of the Gas
supply company. Install the main gas cock near the boiler. The gas connection is loca-
ted at the bottom of the boiler. Fit a gas filter in the gas supply piping to avoid debris in
the gas control unit.
NOTE: The boiler is suitable for both natural gas and propane firing.
It is supplied as standard set for natural gas, therefore an adjustment to the gas valve
and the fan speed setting must be carried out BEFORE the boiler is fired and commis-
sioned for the first time on propane (ref. Par. 9.1).
57117.indd 3857117.indd 38 1-4-2009 14:35:521-4-2009 14:35:52










