Specifications
• Additional equipment—(Refer to Fig. 16 & Fig. 17).
Item
No.
Component Part Mfgr. Description Technical Bulletin
1
Water Supply Control Valve Select
OS&Y -
Butterfly -
Tamper Switch (Optional) for OS&Y Valve
D
Model OS&Y2
System Sensor
A05-0196
(Optional) for Butterfly Valve Model P1BV2
System Sensor
A05-0197
2 Deluge Valve B Model DDX Reliable 518/519
3 Single Interlock Preaction Trim Kit B Refer to Parts List in this Bulletin Reliable 749
4 Waterflow Alarm Pressure Switch D
Model EPS10-2 (DPDT, UL, FM)
System Sensor
WFDS51701
Model EPSA10-2 (DPDT, ULC)
5 Mechanical Alarm (Optional) B Model C Reliable 612 / 613
6
Releasing / Control Panel
C
Model PFC-4410-RC
Potter #5403550
Batteries
12 VDC, 12 AMP Hours (90 Hours Backup) FM
12 VDC, 7 AMP Hours (60 Hours Backup)
Optional Accessories
CA2Z (Class A Wiring Module for Initiating Circuits)
CAM (Class A Wiring Module for Indicating Circuits)
ARM-1 / ARM-2 (Auxiliary Relay Module)
RA-4410-RC (Remote Annunciator)
7 Alarm Annunciator A
Model SSM24-8 24 VDC / Polarized Bell
-
Model SSM24-10 24 VDC / Polarized Bell
Model MA24-D 24 VDC / Polarized Sounder
Model MASS24LO 24 VDC / Polarized Sounder Strobe
8 Trouble Annunciator A
Model SSM24-6 24 VDC / Polarized Bell
-
Model MA24-D 24 VDC / Polarized Sounder
9 Manual Emergency Station (Elec.) A
Model BNG-1 (SPDT) 1 & 2 Area Detection
-
Model BNG-1F (DPDT) Cross Zoned Detection
10 Pilot Line Detectors B Model F1-FTR Pilot Line Detectors Reliable 180
11 Sprinklers B Closed Type
Reliable 110, 117, 131,
136, etc.
12 Air Compressor E Per NFPA 13 requirements Gast F-30
13 Pressure Maintenance Device B Model A-2 or B-1 Reliable 254
14 - - Model B1 Reliable 323
15 Nitrogen Regulating Device B - -
16 Air Compressor Panel B Model B-SI or C-SI Air Compressor Panel Reliable 254
System Equipment Manufacturers
(A) Notifier
(B) Reliable Automatic Sprinkler Co., Inc.
(C) Potter Electric Signal Company
(D) System Sensor
(E) Gast Mfg, Inc.
46.