Instruction manual
16.
Ordering Information
Specify
Valve Model & Size — 4”(100mm) Model DDX Deluge Valve (P/N 6103040026), 6”(150mm) Model DDX Deluge
Valve (P/N 6103060024), 165mm Model DDX Deluge Valve (P/N 6103060028).
Trim — The trim set is available in individual parts, in time-saving segmentally assembled kit forms, or fully as-
sembled to the Model DDX Deluge Valve with or without a control valve.
Solenoid Valve —175 psi (12,1 bar) or 250 psi (17,2 bar) Rated. Explosion-Proof Solenoid Valve available upon
request.
Trim Part Numbers
Trim Confi gurations
4” (100mm)
Valve
6” (150mm)
Valve
165mm Valve
Fully Assembled to DDX Valve w/Control Valve 6505040230 6505060230 Not Available
Fully Assembled to DDX Valve w/o Control Valve 6505040231 6505060231 6505065231
Segmentally Assembled (DDX Valve Sold Separately) 6503001707
Individual Parts (DDX Valve Sold Separately) 6503001706
Fully Assembled to DDX Valve w/Control Valve 6505040240 6505060240 Not Available
Fully Assembled to DDX Valve w/o Control Valve 6505040241 6505060241 6505065241
Segmentally Assembled (DDX Valve Sold Separately) 6503001709
Individual Parts (DDX Valve Sold Separately) 6503001708
Note: For metric installations, a 2” NPT x R2, ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold Separately as an
adapter for the single drain outlet of the trims.
Additional Equipment (Refer to Fig. 7)
Item
No.
Component Part Mfr. Description Technical Bulletin
1
Water Supply Control Valve Select
OS&Y, 4”(100mm), 6” (150mm) or 165mm -
Butterfly, 4”(100mm), 6” (150mm) or 165mm -
Tamper Switch (Optional) for OS&Y Valve
D
Model OS&Y2 System Sensor A05-0196
(Optional) for Butterfly Valve Model P1BV2 System Sensor A05-0197
2 Deluge Valve B Model DDX, 4”(100mm), 6” (150mm) or 165mm Reliable 510 / 511
3 Single Interlock Trim Kit B Refer to Parts List in this Bulletin Reliable 727
4 Waterflow Alarm Pressure Switch D
Model EPS10-2 (DPDT, UL, FM)
Model EPSA10-2 (DPDT, ULC)
System Sensor A05-0176
5 Mechanical Alarm (Optional) B Model C
Reliable
612 / 613
6
Releasing / Control Panel
C
Model PFC-4410-RC
Potter 5403550
Reliable 700
Batteries
12 VDC, 12 AMP Hours (90 Hours Backup) FM
12 VDC, 7 AMP Hours (60 Hours Backup)
Optional Accessories
CA2Z (Class A Wiring Module for Initiating Circuits)
CAM (Class A Wiring Module for Indicating Circuits)
ARM-1 / ARM-2 (Auxiliary Relay Module)
RA-4410-RC (Remote Annunciator)
7 Alarm Annunciator A
Model SSM24-8 24 VDC / Polarized Bell
Reliable 700
Model SSM24-10 24 VDC / Polarized Bell
Model MA24-D 24 VDC / Polarized Sounder
Model MASS24LO 24 VDC / Polarized Sounder Strobe
8 Trouble Annunciator A
Model SSM24-6 24 VDC / Polarized Bell
Reliable 700
Model MA24-D 24 VDC / Polarized Sounder
9 Manual Emergency Station (Elec.) A
Model BNG-1 (SPDT) 1 & 2 Area Detection
Reliable 700
Model BNG-1F (DPDT) Cross Zoned Detection
10 Detection Various Smoke, Heat Detectors, etc. Reliable 722
11 Sprinklers B Closed Type
Reliable 110, 117, 131,
136, etc.
12 Supervisory Air Pressure Supply B
Model B Air Compressor Panel
Reliable 252
Model C Pressure Maintenance Device
System Equipment Manufacturers
A) Notifier (C) Potter Electric Signal Company
(B) The Reliable Automatic Sprinkler Co., Inc. (D) System Sensor
•
•
•
•
175 psi (12,1 bar)
Rated Solenoid Valve
250 psi (17,2 bar)
Rated Solenoid Valve
{
{