Instruction manual

16.
Ordering Information
Specify
Valve Model & Size — 4”(100mm) Model DDX Deluge Valve (P/N 6103040026), 6”(150mm) Model DDX Deluge
Valve (P/N 6103060024), 165mm Model DDX Deluge Valve (P/N 6103060028).
Trim — The trim set is available in individual parts, in time-saving segmentally assembled kit forms, or fully as-
sembled to the Model DDX Deluge Valve with or without a control valve.
Solenoid Valve —175 psi (12,1 bar) or 250 psi (17,2 bar) Rated. Explosion-Proof Solenoid Valve available upon
request.
Trim Part Numbers
Trim Con gurations
4” (100mm)
Valve
6” (150mm)
Valve
165mm Valve
Fully Assembled to DDX Valve w/Control Valve 6505040230 6505060230 Not Available
Fully Assembled to DDX Valve w/o Control Valve 6505040231 6505060231 6505065231
Segmentally Assembled (DDX Valve Sold Separately) 6503001707
Individual Parts (DDX Valve Sold Separately) 6503001706
Fully Assembled to DDX Valve w/Control Valve 6505040240 6505060240 Not Available
Fully Assembled to DDX Valve w/o Control Valve 6505040241 6505060241 6505065241
Segmentally Assembled (DDX Valve Sold Separately) 6503001709
Individual Parts (DDX Valve Sold Separately) 6503001708
Note: For metric installations, a 2” NPT x R2, ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold Separately as an
adapter for the single drain outlet of the trims.
Additional Equipment (Refer to Fig. 7)
Item
No.
Component Part Mfr. Description Technical Bulletin
1
Water Supply Control Valve Select
OS&Y, 4”(100mm), 6” (150mm) or 165mm -
Butterfly, 4”(100mm), 6” (150mm) or 165mm -
Tamper Switch (Optional) for OS&Y Valve
D
Model OS&Y2 System Sensor A05-0196
(Optional) for Butterfly Valve Model P1BV2 System Sensor A05-0197
2 Deluge Valve B Model DDX, 4”(100mm), 6” (150mm) or 165mm Reliable 510 / 511
3 Single Interlock Trim Kit B Refer to Parts List in this Bulletin Reliable 727
4 Waterflow Alarm Pressure Switch D
Model EPS10-2 (DPDT, UL, FM)
Model EPSA10-2 (DPDT, ULC)
System Sensor A05-0176
5 Mechanical Alarm (Optional) B Model C
Reliable
612 / 613
6
Releasing / Control Panel
C
Model PFC-4410-RC
Potter 5403550
Reliable 700
Batteries
12 VDC, 12 AMP Hours (90 Hours Backup) FM
12 VDC, 7 AMP Hours (60 Hours Backup)
Optional Accessories
CA2Z (Class A Wiring Module for Initiating Circuits)
CAM (Class A Wiring Module for Indicating Circuits)
ARM-1 / ARM-2 (Auxiliary Relay Module)
RA-4410-RC (Remote Annunciator)
7 Alarm Annunciator A
Model SSM24-8 24 VDC / Polarized Bell
Reliable 700
Model SSM24-10 24 VDC / Polarized Bell
Model MA24-D 24 VDC / Polarized Sounder
Model MASS24LO 24 VDC / Polarized Sounder Strobe
8 Trouble Annunciator A
Model SSM24-6 24 VDC / Polarized Bell
Reliable 700
Model MA24-D 24 VDC / Polarized Sounder
9 Manual Emergency Station (Elec.) A
Model BNG-1 (SPDT) 1 & 2 Area Detection
Reliable 700
Model BNG-1F (DPDT) Cross Zoned Detection
10 Detection Various Smoke, Heat Detectors, etc. Reliable 722
11 Sprinklers B Closed Type
Reliable 110, 117, 131,
136, etc.
12 Supervisory Air Pressure Supply B
Model B Air Compressor Panel
Reliable 252
Model C Pressure Maintenance Device
System Equipment Manufacturers
A) Notifier (C) Potter Electric Signal Company
(B) The Reliable Automatic Sprinkler Co., Inc. (D) System Sensor
175 psi (12,1 bar)
Rated Solenoid Valve
250 psi (17,2 bar)
Rated Solenoid Valve
{
{