Technical data

Potter Program #7
Single Interlock Programming Instructions (Single
Hazard - Cross-Zoned, 2 Alarm Zones, 1 Water ow
Zone and 2 Supervisory Zones)
Apply power to panel.
Slide the program switch down.
Press the FUNCTION button until the display reads “PASS-
WORD = 000.”
To enter a password, press the SELECT button until the
proper number is displayed above the “^” symbol; then
press the SET button to move to the next digit. After enter-
ing the third number the display will change. (All panels are
shipped with a “000” password).
1.
2.
3.
4.
Press the FUNCTION button until the display reads “PRO-
GRAM ##.” (the second “#” character refers to the current
program number between “0” and “24”).
Press the SELECT button until the display reads “PRO-
GRAM #7.”
Press the SET button.
The panel is completely programmed except for the cus-
tom banner and zone messages. Slide the program switch
back up.
5.
6.
7.
8.
INPUTS: 2 conventional zones (cross-zoned), 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS: 1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.
OPERATION: Activation of both conventional zones at the same time will operate the solenoid release circuit and
thegeneral alarm bell.Activation of either conventional zone will operate the general alarm bell.Acti-
vation of the waterflow zone will operate the waterflow bell.Activation of either the low air zone or the
supervisory zone will operate the supervisory bell.When either Zone #1 or #2 is in alarm, Output #1
(general alarm) will operate.When Zones #1 and #2 are in alarm at the same time, Output #4 (solenoid
release) and Output #1(general alarm) will operate.When Zone #3 is in alarm, Output #2 (waterflow
bell) will operate.When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory
bell) will operate.
* The Butter y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #7
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Conventional
#3
Water ow
#4
Low Air Supervisory
#1 ALARM X X
#2 WATERFLOW X
#3 SUPERVISORY X X
#4 RELEASE X X
17.