Technical data
POTTER PROGRAM #6
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Manual Release
#3
Waterfl ow
#4
Low Air Supervisory
#1 ALARM X X
#2 WATERFLOW X
#3 SUPERVISORY X X
#4 RELEASE X X
Potter Program #6
Single Interlock Programming Instructions (Single
Hazard; 2 Alarm Zones, 1 Waterfl ow Zone, and 2
Supervisory Zones)
Apply power to panel.
Slide the program switch down.
Press the FUNCTION button until the display reads “PASS-
WORD=000.”
To enter a password, press the SELECT button until the
proper number is displayed above the “^” symbol; then
press the SET button to move to the next digit. After enter-
ing the third number the display will change. (All panels are
shipped with a “000” password.)
1.
2.
3.
4.
15.
Press the FUNCTION button until the display reads “PRO-
GRAM ##.” (the second “#” character refers to the current
program number between “0” and “24”).
Press the SELECT button until the display reads “PRO-
GRAM #6.”
Press the SET button
The panel is completely programmed except for the cus-
tom banner and zone messages. Slide the program switch
back up.
5.
6.
7.
8.
INPUTS: 1 conventional zone, 1 manual release zone, 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS: 1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.
OPERATION: Activation of either the conventional zone or the manual release will operate the solenoid release
circuitand the general alarm bell.Activation of the waterflow zone will operate the waterflow bell.Acti-
vation of either the low air zone or the supervisory zone will operate the supervisory bell.When either
Zone #1 or #2 is in alarm, Output #1 (general alarm) and Output #4 (solenoid release) willoperate.
When Zone #3 is in alarm, Output #2 (waterflow bell) will operate.When either Zone #4 or the supervi-
sory zone is activated, Output #3 (supervisory bell) will operate.
* The Butterfl y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.