Operator`s manual
Q-DL-2100 Operatorʼs Manual
Quaesta Instruments, LLC (520) 449-3806 • Email: support@quaestainstruments.com
13
// Power Conservation Configuration
// -----These params are active only if Battery Thresholding
// -----is On or Daily Power Conservation is On
Conserve5VPwr= ? - Turns OFF/ON 5V Regulated Power Conservation, 0 or 1
Conserve12VPwr= ? - Turns OFF/ON 12V Regulated Power Conservation, 0 or 1
ConserveNPMPwr= ? - Turns OFF/ON NPM Power Conservation, 0 or 1
// Battery Thresholding
BatteryThresholdsOn= ? - Turns OFF/ON Battery Thresholding, 0 or 1
LowBatteryThresh= ?.?? - Battery voltage below which logger will enter power saving mode
e.g. LowBatteryThresh=11.5
ChargedBatteryThresh= ? - Battery voltage above which logger will leave power saving mode
e.g. ChargedBatteryThresh=12.5
// Daily Power Up and Down Times - see ConservePwrXXX params above
DailyPwrConserveOn= ? - Turns OFF/ON Power Conservation by Time, 0 or 1
DailyPowerUpHHMM= ? - Sets Power Up Time for each day (leaving Power Conservation
Mode)
e.g. ʻDailyPowerUpHHMM=0630ʼ
DailyPowerUpHHMM= ? - Sets Power Down Time for each day (entering Power Conservation
Mode)
e.g. ʻDailyPowerDownHHMM=2130ʼ
// Remote Communications
UseRS232= ? - Turns OFF/ON Use of external RS232 ports, 0 or 1
RS232BaudRate= ? - Baud Rate for External RS232 Ports (best if 19200 or above)
UseSatModem= ? - Turns OFF/ON Use of Iridium Sat Modem, 0 or 1
// Satellite Modem Communication
// Only active if UseRS232=0 and UseSatModem=1
// Iridium Satellite Modem must be present and Activated.
RecordsPerSatTrans= - Number of RecordPeriods before Sat Trans Attempted
MaxRapidSatSigQueries= - Number of Sat Sig Strength Queries before Sat Siq Query aborted
SatRetryPeriod_Minutes= - Number of Minutes to wait for subsequent Trans attempts after
failures
SatTransPersistence= - Number of Sat Trans Retries Before Trans Aborted, 1 to 3
UpdateTimeViaSat= - Turns OFF/ON Updating of Logger Real Time Clock with
Iridium Satellite Network Time, 0 or 1