Tus neeg siv phau ntawv

10/2021 · User Manual Version 1.0 · valid from firmware version 3.1.22
15
WEBLOG 250
First you specify whether the search shall be done by primary or secondary addressing. There is a fast method
and an intensive method with more retries and more tolerant timing (slowly but safer in case of wide M-Bus
networks with many meters). If the installed M-Bus meters have not been programmed with a unique primary
address, you must perform a search for secondary addresses.
The progress of the search for meters is displayed in a window.
All detected meters will be entered into the list of meters after the search for meters has finished. Meters
which have been found during a search for secondary addresses get the primary address (PA) 0 in the list.
The column ID contains the identification which is part of the secondary address. The following columns are:
manufacturer (MAN), version number (VER) and medium. BAUD indicates the baudrate of each meter on the
M-Bus. The navigation buttons on the right side can be used to navigate within the list of meters. The right
arrow shows more settings (columns) of the visible meters (log interval, group, Text1, Text2).You can scroll
up and down with the single arrows by 12 and with the double arrows by 120 meter entries.