Instruction Manual

Regency Bellavista™ B41XTCE Gas Fireplace
35
INSTALLATION
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a 1/8"
wide at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits speci ed on the safety
label.
6) When nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" at
screwdriver. Note: Screw should be snug,
but do not over tighten.
HIGH ELEVATION
This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
B41XTCE -NG System Data
For 0 to 4500 feet altitude
Burner Inlet Ori ce Sizes: #30
Max. Input Rating 42,500 Btu/h
Min. Input Rating 30,000 Btu/h
Supply Pressure min.5.0" w.c.
Manifold Pressure
(High) 3.5"+/- 0.2" w.c.
Manifold Pressure
(Low) 1.6"+/- 0.2" w.c.
B41XTCE - LP System Data
For 0 to 4500 feet altitude
Burner Inlet Ori ce Sizes: #49
Max. Input Rating 37,500 Btu/h
Min. Input Rating 29,500 Btu/h
Supply Pressure min.11.0" w.c.
Manifold Pressure
(High) 10"+/- 0.2"w.c.
Manifold Pressure
(Low) 6.4"+/- 0.2"w.c.
PILOT ADJUSTMENT
Note: If you have an incorrect ame pattern,
contact your Regency
®
dealer for
further instructions.
Incorrect ame pattern will have small,
probably yellow ames, not coming into
proper contact with the rear burner or ame
sensor.
Burner
Flame Sensor
Pilot
Ignitor
Periodically check the pilot ames. Correct
ame pattern has two strong blue ames:
1 owing around the ame sensor and 1
owing across the burner (it does not have
to be touching the burner).
886 S.I.T. VALVE DESCRIPTION
1) Manual high/low adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
1
3
2
4
5
6
7