REGENCY Model 4720 Control/Communicator Installation Manual Part Number 150476, Rev.
Interactive Technologies, Inc. 2 2 6 6 S e c o n d S t r e e t N o r t h N o r t h S a in t P a u l , M N 5 5 1 0 9 - 2 9 0 0 T : 6 5 1 / 7 7 7 - 2 6 9 0 F : 6 5 1 / 7 7 9 - 4 8 9 0 TE C H N O L O G IE S Security Automation Fire Protection Access Control Visit our website at www.ititechnologies.com ITI and Regency are registered trademarks of Interactive Technologies, Inc. ITI © 1998. All rights reserved.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Notices FCC Part 15 Information to the User Changes or modifications not expressly approved by Interactive Technologies, Inc. can void the user’s authority to operate the equipment. FCC Part 15 Class B This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.12 3.13 Jumper Blocks and Jumper Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.12.1 Jumper Block J1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.12.1 Jumper Block J2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.12.1 Jumpers J3 and J4 . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 10.4 10.5 11 Internal Speaker Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Model 4180 Status Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Telephone Line Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 11.1 Line 1 Wiring . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 15.2 Audible Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 15.2.1 Touchpad Alert Tones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 15.2.1 15.3 16 Revised 10/98 Bell Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 17 Preprogrammed EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 17.1 Factory-Programmed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 17.1.1 System Options: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 17.2 18 Revised 10/98 17.1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 List of Tables Red LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Current Draw on Protective Devices LEDs 2 and 3 (F2 and F3) . . . . . . . . . . 22 Wiring the Touchpads to the Model 4720 . . . . . . . . . . . . . . . . . . . . . . . . 29 Switches to Open to Select Sensor ID Numbers . . . . . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 List of Figures Connecting the Supervised Siren Module to the Model 4724 . . . . . . . . . . . . . . . . . . . . . . . 4 Knockout Plug Installation Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4720 Printed Circuit Board, Revision L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4720 Printed Circuit Board, Prior to Revision L . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 1 Revised 10/98 Introduction The ITI® Model 4720 is a combination Control/Communicator which features 16 internal zones. Through the use of zone expanders, the Model 4720 can have up to 80 zones. The zones can be programmed for a wide variety of functions. The Model 4720 can be used in both residential and commercial applications depending on the peripherals and programming options selected.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) • • • • • • • • • • • • • • • • • • • • 2 Revised 10/98 Model 4150 External Control Module. This module may be used for remote control of doors, timed control of lights and remote sensing of temperature, humidity, fluid level, and air flow. Model 4160 Supervised Bell Module. This module must be used when installing the Model 4720 for NFPA 72A. Model 4165 Transformer Housing for NFPA installations.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 4. This device cannot be adjusted or repaired in the field. In case of trouble with the device notify the installing company or return to: Interactive Technologies, Inc. 2266 North Second Street North St. Paul, MN 55109 651/777-2690 800/777-5484 5. If installed in accordance with UL 864, this device must be used with loop start systems only. 2.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 4. The Bell Test at Arming option or the Ringback at Closing option must be selected. 5. Both panic hardwire loops and touchpad zones must be programmed as silent. 6. The ICOM timeout must not exceed 90 seconds. 2.3.2.2 Programming Restrictions 1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 2.3.4 Revised 10/98 NFPA 72 Central Station Signaling and Local Protective Signaling Systems (UL 864) All commercial fire installations must comply with the following, plus the separate requirements for NFPA 71 and/or NFPA 72A, whichever apply. 1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 7. All unused knockout holes must be plugged using bolts and washers (available from ITI, Model 7600, six sets per package). To do this, follow the directions below (see Figure 2.3.5a): 1. Remove all unused knockouts. 2. Install the carriage bolt and three washers as shown in the diagram below. 3. Firmly tighten the wing nut. Note: The smallest washer should be placed on the inside of the hole in the cabinet.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 2.3.6 Revised 10/98 Fire System Test Procedure for UL 985 Systems In a residential fire system, it is required to periodically test the bell (or bells) on standby power only. This test must be performed weekly according to the following procedure: 1. Call the central station and report that you are going to conduct a test. 2. Make sure that the system is not armed. 3.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.1 Revised 10/98 Battery Cables The red (+) and black (–) battery cables are used to connect a 12-VDC rechargeable battery (Model 6712— not provided) to the system. The battery provides backup power to the Model 4720 in the event of AC power interruptions (failures). CAUTION: Observe proper polarity when connecting the battery cables of the Model 4720. Note: The Model 6712 12V, 6.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Fuses 3.3.2 PC board revisions prior to Revision L still use Revisions A-K for overcurrent protection. • • • • F1 is a 2.5-A Fast Blow Fuse that provides overcurrent protection for an AC Siren Speaker connected to Terminal 4 of the Model 4720. F2 is a 1.5-A Fast Blow Fuse that provides overcurrent protection for touchpads and any accessories connected to Terminal 5 of the Model 4720. F3 is a 1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.6 Revised 10/98 AC Power Light The green AC power light is on whenever AC power is present, the DC power switch is in the ON position and all fuses are intact. 3.7 Touchpad Volume Control The touchpad volume control is a potentiometer which controls the volume of the trouble alert and annunciator tones at the internal speakers. Rotate the control clockwise to increase the volume. 3.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Be sure to maintain a physical separation of at least one-half inch between the field wires and any expansion device connection points. This will prevent transient damage to the connection points.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 P6: 4140 Intercom/Telephone/Listen-in or 7369 Listen-in 1 2 3 4 5 6 7 8 9 10 11 3.12 GND +12 V (LED 2 or Fuse F2) LISTEN ENABLE OUT /DIAL CONTROL AUDIO ENABLE OUT CONTROL AUDIO OUT TELEPHONE AUDIO EARTH GND SWITCHED RING1 HOUSE RING1 HOUSE RING2 Jumper Blocks and Jumper Wires Note: Starting with PC board Revision J, J1 and J2 are jumper blocks instead of jumper wires.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.13 Revised 10/98 Plug-On Terminal Strips The Model 4720 uses plug-on terminal strips, which allow you to change the panel without unscrewing each terminated wire. 3.13.1 Terminal Strip Removal 1. Tag each of the four (4) terminal block wire bundles, so the blocks can be reinstalled in the correct positions. 2. Disconnect the 9220 AC Transformer and the battery cables. 3.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.14 Model 4720 Terminal Strip Description Terminal # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Revised 10/98 Terminal Description AC input AC input Earth Ground Siren Power Auxiliary (Bell) Power Electrical Ratings 16.5 VAC, 60 Hz, 40 VA 16.5 VAC, 60 Hz, 40 VA 16 VDC unregulated (1-A load) max.*1 10.2 VDC - 13.7 VDC, 1 A max.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 3.15 Revised 10/98 Non-UL Wiring Diagram For UL installations, refer to the wiring diagram mounted in the front cover of the Model 4720 only. This diagram contains items which are not currently acceptable for UL installations. These items are the Model 4203 Touchpad, PLC Connector, 7140 relays, and external siren driver. The UL wiring diagram also contains various electrical ratings and restrictions. Figure 3.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 4 Revised 10/98 4720 Control Panel Overview 4.1 Current Draw Calculations 4.1.1 Total Standby and Alarm Current Draw Table 4.1.1.0a is a worksheet to help you calculate the amount of current the system draws on standby and in an alarm condition, to make sure the installation does not exceed power supply and calculating current draw for battery capacity.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 4. Add up each of the two Total columns and write the totals in the spaces on the last line (4th page) of the worksheet. When you add the columns, remember to: • Include the values from ALL three (3) pages of the worksheet (Table 4.1.1.0a). • Include both printed and handwritten values. 5.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Table 4.1.1.0a: Current Load Worksheet Device LED (Revision L & Later) Fuse # (Prev. Revs.) 4140 Intercom/Telephone Controller 2 F2 4150 Auxiliary Control Module 3 4640 Intercom Station 3 4724 Control Expander — 5260 Printer Interface 3 7369 Two-Way Audio Listen-in Module 2 # of Devices (Max.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Table 4.1.1.0a: Current Load Worksheet Device LED (Revision L & Later) Fuse # (Prev. Revs.) # of Devices (Max. Allowed) Model 7181 Universal Zone Converter 5 F3 (1 per zone max.) Wheelock Bell 2 F2 3 max.) 8-ohm Speaker 2 F2 (1 max.) 45-ohm Speaker 2 F2 (6 max.) Siren (15-watt speaker) 1 F1 (1 max.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 4. Subtract the second value in Column 3 from the first value in Column 3. (Total alarm current – Alarm current NOT associated with LED 2 or 3) The total combined Alarm current draw on these protective devices must not exceed 1300 mA. To obtain more active current, touchpads can be powered by the Model 4195, which provides an additional 2500 mA. Table 4.1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 4.2 System Planning Block Diagram Figure 4.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 5 Revised 10/98 Wiring Precautions To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high current output and power wiring. Induced noise can interfere with telephone communication, or even cause false alarms. Avoid pulling one multiconductor cable for the entire panel.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 6.2 Revised 10/98 Mounting the Model 4720 Mount the Model 4720 so it is firmly secured to the wall surface. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the concrete surface and then attach the Model 4720 to the plywood. Mount all other desired components to the plywood interface. Figure 6.2a: Suggested Mounting for the Control Panel 6.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 6.3.2 Revised 10/98 Installing the Transformer The main wiring diagram and Figure 6.3.2a show the connection of shielded 2-conductor cable and the Model 7890 Transient-Surge Protector to the Model 9220 UL Listed Class II Power Transformer (16.5 VAC, 40 VA). Both models are included with the Model 4720. The transformer should be plugged into a 120-VAC, 60-Hz continuous duty (unswitched) grounded outlet.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 6.3.2a: Model 9220 Transformer Connection 6.4 Model 4195 Auxiliary Power Supply The Model 4195 provides an additional 2.5 A of current for accessory items, 1.25 each at Terminals 3 and 4. The 4195 contains an AC power light that monitors the transformer. It also allows you to use two (2) standby batteries to double the time that the system can function on battery standby.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 6.4a: Wiring the Model 4195 Auxiliary Power Supply 7 Touchpad Installation Note 1: In a UL installation, the touchpads must be mounted on a dual gang electrical box. Note 2: If a touchpad is removed from a Model 2605/2607 and then connected to a Model 4720, the CHM and CODE2 keys won't function.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 7.2 Revised 10/98 Wiring the Touchpads All touchpads require four (4) wires to operate. The 4-conductor cable can be up to 1,000 feet long. The minimum wire gauge is 22 AWG for runs under 500 feet and 18 AWG for runs between 500 and 1,000 feet. Wire the touchpads as shown in Table 7.2a. Table 7.2a: Wiring the Touchpads to the Model 4720 Touchpad Terminal # 1 2 3 4 7.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 7.4 Revised 10/98 Setting ID Codes When installing the system, set the ID number for each touchpad according to the following procedure: 1. Apply power. 2. Press 0, 0, TEST (before pressing any other key sequence). 3. The display will read KEY ID=NN, BEEP=1 (NN represents the current ID number. BEEP=1 indicates that the miniature speakers in the touchpads have been enabled.) The beep enable can be toggled by pressing MUTE.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 7.6 Revised 10/98 Mechanical Keyswitch A normally open mechanical keyswitch may be wired between Terminals 14 (loop power) and 38 (Zone 16). Figure 7.6a shows a mechanical keyswitch connected to the Model 4720 along with Ready and Armed Lights. Note 1: When a mechanical keyswitch is used, you lose the use of Zones 13 through 16.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 9.1 Revised 10/98 Normally Open and Normally Closed Contact Wiring * Supervision of either N.O. or N.C. contacts is optional (see the Model 4720 Programming Options Description Manual, P/N 150299). Note 1: When supervising normally open contacts, a 15-kΩ end-of-line resistor must be used. Note 2: When using normally closed contacts, a 15-kΩ resistor must be installed in series with the loop.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 9.2a: ESL 445AT Smoke Detector Wiring 9.3 Model 7181 Fire Zone Converter The Model 7181 Fire Zone Converter allows you to connect style A (formerly class B) sensors to the Model 4720's style D (formerly class A) zones, to connect style D sensors to the Model 4720's style A zones, and to connect 2-wire smoke detectors to the Model 4720's 4-wire zones.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 See Table 4.1.1.0a (Section 4.1: Current Draw Calculations) for current rating. Figure 10.1a: Model 4160 Supervised Bell Module Wiring 10.1.1 Auxiliary Power for Supervised Bells The maximum bell current draw from Terminal 5 of the Model 4720 is 375 mA for NFPA 72 Local Protective Signaling Systems, UL 864 installations. This equates to three (3) bells maximum (125 mA each).
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 AC 4160 4195 1.25 A EACH 1 9227 18 VAC 6 1 6 +12 V +12 V GND SUPERVISION +12 V MODEL 7630 EOL RESISTOR + + _ _ 22 BELLS (1A MAX TOTAL) 7 6 1 4720 ZONES 34* 23 38 *TERM. 34 (ZONE 12) USED AS AN EXAMPLE 0476G15A.DSF Figure 10.1.1a: Auxiliary Power for Supervised Bells 10.2 Commercial Burglary Bell Wiring Figure 10.2a shows the wiring of an external DC alarm bell.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 10.2a: Commercial Bell Wiring 10.3 External Speaker Wiring Terminal 4 (Ext. Spkr.) of the Model 4720 is designed for use with an 8-Ω, 15-W speaker. Connect the speaker between Terminals 4 and 7 as shown in the diagram below. DO NOT cut Jumper J1 on the Model 4720. If the board has a shunt block, leave it in the right (“in”) position. An external speaker is NOT permitted for UL commercial installations.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 10.4 Revised 10/98 Internal Speaker Wiring If an internal speaker is to be used such as in a touchpad, it must be connected between Terminal 5 (auxiliary power, speaker +) and Terminal 8 (speaker –). The 4720 was designed for use with an 8-Ω, 9-W internal speaker or up to six 45-Ω, 1-W speakers. If you wish to have alarm sounds only on some speakers, then cut Jumper J2 (move shunt block to the left/ “out” position).
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 11 Revised 10/98 Telephone Line Connection 11.1 Line 1 Wiring The Model 4720 communicates to the central station over the same telephone line already installed in your home or building. You should connect the Model 4720 to the phone line using an RJ31X type phone jack. The telephone company will install an RJ31X jack upon request.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 11.3 Revised 10/98 External Dialer Failed Indicator A 12-VDC device such as an indicator lamp or the coil of a 12-VDC relay may be wired as a dialer failed indicator. To use a dialer failed indicator, connect the positive side of the indicator to Terminal 5 (auxiliary power) and the negative side to Terminal 40 (dialer failed). In UL applications, this signal is provided from the touchpads. Figure 11.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 11.4.2 Revised 10/98 Model 4175 Operation The 4720 will always try to use Phone Line 1 unless it is bad. If Phone Line 1 is bad, the Model 4720 automatically chooses Line 2. If the Model 4720 fails to communicate on its first attempt (on either line), it will automatically switch to the alternate phone line.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 12.1.1a: Wiring the Model 4110 Serial Zone Expander The Model 4100 SmartSensor contains a magnetic reed switch for sensing alarms. The Model 4101 provides two (2) terminals for connecting either normally open or normally closed contacts. Both models provide two (2) terminals for connection to the Model 4110 Zone Expander.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 The Model 4110 has two (2) serial loops. Each loop may have up to 30 Model 4100 and Model 4101s in any combination. If you will be using 30 sensors or less, they should all be placed on Loop 1 (Terminals 1 and 2 of the Model 4110). Terminal 1 is the positive terminal for Loop 1 and Terminal 2 is the negative terminal for Loop 1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 12.1.2 Revised 10/98 Determining ID Numbers and Zone Numbers 12.1.2.1 Calculating 4110 ID Numbers from Zone Numbers To insure that the sensors activate the appropriate zones, you must assign the correct ID numbers to the sensors.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 12.2 Revised 10/98 Model 4115 Serial Zone Expander The Model 4115 is a UL Listed 2-wire serial zone expander for the Model 4720/4724 Control/ Communicator that allows up to 64 switches to be connected on a single pair of wires. The 12/91 Regency binder update contained a preliminary version of the documentation for the Model 4115.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 12.3.1b shows how to wire the Model 4125 to a 4000 series control panel. Figure 12.3.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 12.3.2 Revised 10/98 Determining 4125 Zone Expander's Input and Zone Numbers Note: Output numbers are not calculated for the Model 4125 because the outputs are not numbered—they are labeled “COM”. 12.3.2.1 Calculating 4125 Input and Zone Numbers The zone number is the number displayed on touchpads and reported to the central station. The input number is the screw terminal number silk-screened on the Model 4125 PC board.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 12.4.1a: Wiring the Model 4130 RF Zone Expander and Model 4135 Remote Receiver 12.4.2 Programming the Transmitters See the Model 4130/35 Installation Manual (P/N 150474). 13 Model 4184 Watchdog Module 13.1 Model 4184 Watchdog Module Wiring The Model 4184 Watchdog Module connects to the Model 4720 Control/Communicator in order to comply with NFPA commercial fire protection equipment standards.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 The Model 4184 Watchdog Module is installed in the Snap-trak, and connects to the Model 4720 control communicator through a 4-conductor cable (P/N 130235) in the following manner: Wire Color Brown Red Orange Yellow 13.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 14.1a: Connecting the Model 4140 to the Model 4720 14.1.1 Mounting the Model 4640 The Model 4640 is designed to be mounted next to a touchpad at its right side. The plastic prongs sticking out of the Model 4640 are for attachment to a touchpad. To mount: 1. Remove the touchpad's back plate. 2. Remove the hidden alignment notch on the right side of the touchpad plate.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 14.1.1a: Model 4640 Audio Module 14.1.2 Mounting the Model 4640 as a Stand-Alone Intercom If the Model 4640 will never need to be attached to a touchpad, the plastic prongs on the left side of the module can be removed. Move the prongs back and forth a few times. They should break off easily. Secure the back plate of the Model 4640 to a wall using pan head screws only.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Table 14.1.3a: Connecting the Model 4640 4640 Pin # 4140 Terminal # Description GND +12 VDC +SX MX GND 1 2 3 4 5 Ground Auxiliary power Speaker signal (+) Microphone signal Speaker signal (–) Wire Color Black Brown Green White Red The Model 4640 has a microphone gain adjustment located on the back of the unit.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 14.1.4 Revised 10/98 7381 Connecting the Model 4140 to the Model 7381 Front Door Intercom Station The Model 7381 is an outdoor intercom station intended for use with the Model 4720/4140 Control/ Communicator with Intercom. The Model 7381 contains a microphone with amplifier, a 20-ohm speaker, a light used by visitors to locate the unit and a normally open push-button switch.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 14.2 Revised 10/98 Model 4150 Environment Control See the Model 4150 Auxiliary Control Module Installation Manual (P/N 150475). 14.3 Printing Devices 14.3.1 Model 5255 On-Site Printer (Discontinued) For 5255 installation instructions, refer to the Model 5255 Installation Manual (P/N 150296). Note: The Model 5255 uses printer paper with the part number 005257.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Figure 14.4b: Model 7367 with Model 4640 Speaker and Microphone 14.5 Model 7369 Two-Way Audio Listen-in Module The Model 7369 Two-Way Audio Listen-In Module allows for alarm verification and two-way communication. Refer to the Model 7369 Installation Manual (P/N 150605) for more information.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 15 Revised 10/98 Touchpad Operation The following paragraphs describe the functions of the indicators and switches provided on the touchpads. Keep in mind that some of the touchpads do not provide all of the functions listed. If you are using a touchpad that does not have a described function, skip that particular paragraph.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 15.1 Revised 10/98 LED Indications 15.1.1 LEDs on Left Side (Behind Door) Armed LED ON – The system is armed. OFF – The system is disarmed. FLASHING – One or more zones are in an alarm condition. No Delay LED ON – Zones that were programmed as delayed will now act as instant zones, with no delay before generating an alarm. OFF – Exit and entry delayed zones will work as programmed.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 The touchpad speakers will also beep when: • • • • 15.2.2 Bell Sounds • • • 15.3 A key is pressed. Someone has activated the zone display by pressing the BYPS, MEM, or STAT keys. The zone display has been activated by an alarm or zone trouble condition (except silent alarms). An incorrect keyswitch entry has been made. This tone is longer than the other beeps. There may be a delay before it is sounded.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 BYPS This key is used to bypass (deactivate) individual zones (sensors) from system monitoring or control. It also allows you to check which zones have been bypassed. MEM When the system is disarmed, pressing this key turns on the zone lights that correspond to any zones that were in an alarm condition since the last time the system was armed.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16 Revised 10/98 Touchpad Functions 16.1 Viewing Status When the STAT key is pressed the display will show the zones that are not ready to be armed. With Revision N of the Model 4720, if an alarm, trouble, or supervisory condition exists, the LCD scrolls only the words ALARM, TROUBLE, or SUPERVISORY. You can then press STAT to display the zone number and location of trouble and supervisory conditions.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16.4.2 Revised 10/98 To Clear Memory To clear the alarm memory, press MUTE, MEM. Note: The Alarm Memory can store alarms from all 80 zones. However, the alarms are displayed in order by zone number, NOT in the order in which they occurred. 16.5 Chime Function Press CHM while the panel is disarmed to toggle the Chime function. 16.6 Interior Function Press INT to toggle the Interior zones.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16.10.2 Revised 10/98 CODE 2 key (Code 2 Residential Touchpads Only) Code 2 refers to secondary access codes (Codes 10 - 99). Under normal operating conditions, these codes can arm the system only. When Code 2 is enabled, these codes may also be used to disarm the system. 16.10.2.1 To Enable Code 2 Press CODE 2 followed by your access code (0 - 9). At this time, Code 2 will be enabled and the system will be armed. 16.10.2.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16.12.4 Revised 10/98 Request Download This mode causes the dialer to request downloading from a computer installed with Model 5540 Downloading Software. 16.12.5 Program Slot #5 This mode is used to program the Model 4150 Auxiliary Control Module. 16.12.6 Hex Programming The Hex Programming mode is available only to Code 0 (see Section 19: Touchpad Programming for an example).
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16.12.9 Revised 10/98 Set Time Mode When you first apply power to the system, it will come up in the Set Time mode. If you are not in this mode, follow the directions below. 1. Press 9, TEST, followed by a valid access code (0 or 1). The display will show SET TIME. 2. The time setting is six digits in length. The first digit corresponds to the day of the week. The second digit will indicate either AM (0) or PM (1).
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 16.13.5 Revised 10/98 Do Not Disturb As of Revision 880515 of the Model 4140 chip, the intercom has a Do Not Disturb feature: 1. To activate, press 9, ICOM. 2. If anyone tries to contact that station by intercom, they will get a busy tone. 3. To restore normal operation, press ICOM. 16.14 Telephone The telephone feature has the capability to store two (2) phone numbers up to 12 digits in length.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 17 Revised 10/98 Preprogrammed EEPROM 17.1 Factory-Programmed Options The EEPROM (Electrically Erasable Programmable Read Only Memory) contains information that is used by the microprocessors. This information determines what options the system will perform. The 4720 is shipped with an EEPROM that has been factory-programmed with the options listed below so that the system is operational as soon as it is installed.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 17.1.5 Revised 10/98 Timers: Aud Shutdown = 9 (9 × 10 = 90 seconds); Exit Delay = 30 seconds; Entry Delay 1 = 30 seconds; Entry Delay 2 = 60 seconds; Swinger Window = 4 hours; RF Supervision = 24 hours; Door Strike = 6 (6 × 0.8 = 5 seconds); Door Open Max = 60 seconds; Alm Rep Delay = 15 seconds; Special Days = Saturday and Sunday. 17.1.6 Access Options: All functions (DR, BY, CL, OP) enabled for all codes (0-99). 17.1.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 18 Revised 10/98 Programming 18.1 Model 4720 Downloading (with 5540 PC Downloading Software) 18.1.1 The Initial Download The Model 4720 was programmed at the factory to Answer Ring Detect after 10 rings. Once the Model 4720 is installed, the downloading computer can call the Model 4720. After 10 rings, the Model 4720 will answer the call and downloading will begin. 18.1.
LAST EXP. 2 ZONE RESIDENCE CODE # OF AREAS LAST INTERNAL Z. DNLD IF DEFAULT BELL TEST 0 PUC 68 Figure 18.2a: Model 5520 Programmer Menus LISTEN STATIONS MEMORY PH #1 MEMORY PH #2 LISTEN TIME LISTEN TO USE LINE 1 ONLY INTERIOR BYPASSABLE INTERIOR BYPASSABLE CHIME AUTO CLOSE HOURLY TEST DIRECT LINE USE LINE 2 ONLY RING STATIONS ATTEMPTS #4 N.C. CONTACTS AUX CODE MEM DIAL ONLY FORMAT #4 24 HR TROUBLE . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 19 Revised 10/98 Touchpad Programming All options can be addressed in Hex format. Hex programming is not recommended, except as a handy troubleshooting tool. To obtain a Hex programming form, contact ITI Order Entry at 1-800-777-4841. Note: Touchpad programming can only be accomplished through the use of a full-function touchpad with an LCD. WARNING: During programming, the system will not respond to alarms.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 20 Revised 10/98 Area Control Operation Refer to the Model 4721 Area Control Software Instruction Manual (P/N 150483). 21 Model 4720 reporting Formats • SIA (SEIA) The SIA (Security Industry Association) format must be used with a Model 9000 Receiver. Each message will be displayed in English followed by the zone number. • FSK 2 The FSK 2 format is similar to the SIA format.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 9000 Printer Code Revised 10/98 Status of 4720 In the zone types shown below, “Burglary” is used as an example.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 23 Revised 10/98 Trouble/Error Messages The following paragraphs describe the possible trouble and error messages that can be displayed on touchpads using an LCD. 23.1 Troubles PAPER Printer is out of paper. DATA LOST Dialer has failed all of its attempts to communicate with the central station and the Model 4720 has deleted the message(s) it was trying to send. FAILED Dialer cannot communicate with the central station.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 DOOR (1 - 15) Indicates a door has been left open (or forced open) when using the door contact feature with commercial touchpads (see Note 2 below). 1 - 80 Indicates which zone is in trouble. When the RF system is used, the first line of the display will show either LOW BATTERY or TROUBLE. The second line of the display will show which zone has a low battery or which zone is in trouble.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Next, use a clip wire and short the two (2) wires together at the far end of the cable, away from the ohmmeter. You should now see almost no resistance on your ohmmeter. If you continue to see a very high resistance, one or both of the wires have been cut somewhere along the cable run. Try to determine the location of any cuts or shorts in the cable.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Program As Type = Fire 24 hr alarm 24 hr trouble N.O. No shutdown Type = Sprinkler 24 hr alarm 24 hr trouble N.O. 25.2 Revised 10/98 System Response Water flow = Fire alarm Wire break = Fire trouble Valve off = Sprinkler supervisory Wire break = Sprinkler trouble Press MUTE, MUTE + CODE to silence.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) 26 Revised 10/98 REGENCY® ONE YEAR LIMITED WARRANTY Interactive Technologies, Inc. (ITI) warrants that Regency products manufactured by ITI (Regency Product) will be free from defects in material and workmanship for one (1) year from the date of purchase by the original purchaser.
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98 Index 80 code . . . . 8510 Receiver. 8520 Receiver. 8Y code . . . 9000 Receiver. 9Y code . . . Symbols # Rings option $000 address . * key . . . . . . . . . . . . . . . . . . . . . 65 . . . . . . . . . . . . . . . . 69 . . . . . . . . . . . . . . . . 60 Numerics 09 code . . . . . . 0X code . . . . . . 0Z code . . . . . . 1 - 80 message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) reporting codes for . . . . . . resetting . . . . . . . . . . . . silencing. . . . . . . . . . . . touchpad alert tones . . . . . . alert tones . . . . . . . . . . . . . Alm Rep Delay option . . . . . . analog temperature sensor . . . . . Answer Ring Detect option . . . . Answering Machine Bypass feature AR0 code . . . . . . . . . . . . . Area 1 - 8 armed . . . . . . . . . Area 1 - 8 disarmed . . . . . . . . area control . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) clock speed adjustment . . . . . . . . . . . . Close area 1 - 8 printout . . . . . . . . . . . Close ID 0 - 99 printout . . . . . . . . . . . Close zone Y message . . . . . . . . . . . . Closing report . . . . . . . . . . . . . . . . . CO0 code . . . . . . . . . . . . . . . . . . . Code 0 . . . . . . . . . . . . . . . . 5, 66, Code 1 . . . . . . . . . . . . . . . . . . . . Code 11 . . . . . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Digit reported zone . . . . . . . . . . . . . . 70 disabling alarm reporting . . . . . . . . . . . . . . 61 CODE 2 . . . . . . . . . . . . . . . . . 61 disarming the system . . . . . . . . . . . 60, 72 Disp Speed option . . . . . . . . . . . . . . . 65 displaying, alarm memory . . . . . . . . . . . 59 DLY key . . . . . . . . . . . . . . . . . . . 57 DM 0 - 180 code . . . . . . . . . . . . . . . 73 DO 1 - 15 code . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Expansion restore . . . . . . Expansion restore X printout Expansion trouble . . . . . . Expansion trouble X printout expansion zones options . . . external devices . . . . . . . external, speakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 72 71 72 65 75 36 FORCE CLOSE . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) PAPER message . . . . . . . . . . . . . 53 touchpads with . . . . . . . . . . . . . . 66 LEDs bypassing zones and . . . . . . . . . . . 59 excessive current draw . . . . . . . . . . 18 indications . . . . . . . . . . . . . . . . 56 red type . . . . . . . . . . . . . . . . . 11 Watchdog Modules and . . . . . . . . . . 48 limited warranty . . . . . . . . . . . . . . . . 78 LINE 1 message . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) memory location #1 . . . . . . . . . . . . . . 64 memory location #2 . . . . . . . . . . . . . . 64 Memory trouble . . . . . . . . . . . . . . . . 72 menu structure . . . . . . . . . . . . . . . . 68 messages error . . . . . . . . . . . . . . . . . . . 74 trouble . . . . . . . . . . . . . . . . . . 74 system . . . . . . . . . . . . . . . . . . 66 microphones diagram of . . . . . . . . . . . . . . 53, 54 gain adjustment for .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) OR 0 - 99 codes . . . . . . . . . . . Osbourne/Hoffman Quickalert Receiver oscillations . . . . . . . . . . . . . . . outlets . . . . . . . . . . . . . . . . . outputs . . . . . . . . . . . . . . . . overcurrent protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60, . . . 72 73 50 25 75 10 power supply 4194 Auxiliary Power Supply . . . . 4195 Auxiliary Power Supply . . 5, troubleshooting . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) reporting alarms . . . . . . . . . . . . . memory during Auto test . . . . reporting formats . . . . . . . . . . reports, automatic and unconditional . reprogramming EEPROMs. . . . . . Request Download mode . . . . . . requirements FCC . . . . . . . . . . . . . . Grade A Mercantile (UL 365) . hardware . . . . . . . . . . . . preconnection . . . . . . . . . . programming . . . . . . . . . . telephone . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) sprinkler codes . . . . . . . . . . . . . . . . 71 sprinkler supervisory . . . . . . . . . . . . . . 77 Sprinkler supervisory zone type . . . . . . . . 76 Sprinkler trouble . . . . . . . . . . . . . . . . 77 Sprinkler zone . . . . . . . . . . . . . . . . . 73 stand-by current . . . . . . . . . . . . . . 5, 18 STAT key . . . . . . . . . . . . . . 57, 59, 77 status connector . . . . . . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) transmitters, RF type . . . . . . . . . . . . . TROUBLE message . . . . . . . . . 59, 75, trouble messages . . . . . . . . . . . . . . . Trouble or Supervisory option . . . . . . . . . trouble restore . . . . . . . . . . . . . . . . . Trouble zone 0 message. . . . . . . . . . . . Trouble zone 0 was force armed message . . . Trouble zone 9 message. . . . . . . . . . . . Trouble zone B message . . . . . . . . . . .
Regency® Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Y YR0 code YT0 code . . . . . . . . . . . . . . . . . . . 72 . . . . . . . . . . . . . . . . . . . 72 Z Zone 1 (Fire) option . . . . . . . Zone 81 option . . . . . . . . . Zone 82 option . . . . . . . . . Zone 83 option . . . . . . . . . zone expander 1 . . . . . . . . . zone expander 2 . . . . . . . . . Zone expander 1 back to normal Zone expander 1 trouble . . . . . Zone expander 2 back to normal Zone expander 2 trouble .