Specifications
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
9
TECHNICAL DATA (LP SERIES)
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LP(G)(H) 0600-1 1.5 75
LP(G)(H) 0700-1 1.9 82
LP(G)(H) 0950-1 2.2 105
LP(G)(H) 1200-1 3.0 115
LP(G)(H) 1400-1 3.7 137
LP(G)(H) 1800-1 4.1 173
LP(G)(H) 2100-1 5.4 193
LP(G)(H) 2800-1 7.1 248
LP(G)(H) 3500-1 8.9 304
LP(G)(H) 4200-1 10.6 359
TECHNICAL DATA (LA SERIES)
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LAA 0650-1 2.2 100
LAA 0760-1 3.0 108
LAA 0900-1 3.7 131
LAA 1200-1 4.1 174
LAA 1500-1 5.4 190
LAA 1800-1 7.1 235
LAA 2700-1 8.9 272
LAA 3000-1 10.6 345
LAA 3800-1 13.3 438
LAA 4500-1 15.9 517
LAE 0650-2 4.0 107
LAE 0760-2 5.3 123
LAE 0900-2 6.6 141
LAE 1200-2 7.3 187
LAE 1500-2 9.7 219
LAE 1800-2 12.8 256
LAE 2700-2 15.9 315
LAE 3000-2 19.0 412
LAE 3800-2 24.3 508
LAE 4500-2 29.1 605
LA(G)(H) 0650-1  2.2 103
LA(G)(H) 0750-1 3.0 112
LA(G)(H) 0900-1 3.7 133
LA(G)(H) 1200-1 4.1 180
LA(G)(H) 1500-1 5.4 198
LA(G)(H) 1800-1 7.1 240
LA(G)(H) 2700-1 8.9 284
LA(G)(H) 3000-1 10.6 370
LA(G)(H) 3800-1 13.3 455
LA(G)(H) 4500-1 15.9 541
Note: • Operating charges are based on 30% liquid, 70% vapor at 25ºF suction
• Fan motor heat is not included in rating, add 342 BTUH (100W) per fan motor to room load
• Use suffix 1 for 120/1/60, suffix 2 for 240/1/60
• For 200-240/1/50 use suffix 2 and multiply capacity by 0.92
• For R134a or R-22 refrigerant charge, multiply R-404A by 1.09.
• Air throw for LS Series is 25 to 35 feet
• Air throw for LP Series is 12 to 18 feet
• Air throw for LA Series is 10 to 15 feet