Manual

2
EN
Technical details
Values
0 to 18000 Microns / 0 to 2400 Pascal
Pascal, Microns, mbar, Torr, mTorr, psi, inHg
0 20:
0.2 Microns
21 200:
1 Microns
201 500:
5 Microns
501 1000:
10 Microns
1001 3000:
50 Microns
3001 6000:
200 Microns
6001 18000:
1000 Microns
Thermistor
1/4 SAE = 7/16-20UNF
0°C to 40°C / +32°F to 104°F
IP54
-20°C tp +60°C / -4°F to 140°F
34 bar / 500 psi
up to 100 Microns +/- 10 Microns
101 - 750 Microns +/- 45 Microns
3 x 1.5 V AAA / LR03 batteries
Service life when used continually is ca. 40 hours
(depending on the battery type).
After 10 min. if vacuum value greater than 18000
Microns
After 30 min. if vacuum value less than 18000 Microns
Use
Preparation
Insert 3 batteries in the battery compartment at the back of the device.
Ensure the batteries are inserted using the correct polarities.
Do not leave used batteries in the battery compartment. If you
will not be using the device for a longer period of time, remove
the batteries from the battery compartment.