Combi 3004146 EN Installation and operating guide Condensate Pump
English Instruction manual Combi Please read all safety and installation instructions completely before commencing. Contents Introduction 02 General information 02 Important safety notice 02 Technical data 03 Product description 04 Transport and storage 06 Commissioning 06 Maintenance 16 Return and disposal 17 Troubleshooting 17 Replacement parts 18 Appendix 18 Introduction Thank you for purchasing our all-new Combi condensate pump.
English DO NOT use tools to connect the tubing. DO NOT operate this product in ambient temperatures below 5 °C (41 °F). DO NOT operate with incoming water above a temperature of 40 °C (104 °F). Ensure the evaporator coils are free of chemicals before reinstallation of the REFCO Combi pump. CAUTION: This appliance incorporates an earth connection for functional purposes only. Power cable 11 must not be entered with a tensile load.
10 English Abdeckung Instruction manual Combi Product description Combi Kit beinhaltet 1 Diagnostic LED 2 USB port Mitgeliefertes Zubehör 3 DIP-switches 4 Water sensor socket 5 Pump body 6 Factory-installed fuse 7 Digital sensor Alarmkabel Stromversorgungskabel 8 Replacable filter Diagnose-LED 6 USB-Anschluss Dip-Schalter 1 2 3 Stecker Wassersensor Pumpenkörper Werkseitig installierte Sicherung 4 5 6 7 8 9 Digitaler Sensor Austauschbarer Filter Sensorgehäuse Sensorkabel 6 9 Water sensor 7 8 S
Instruction manual Combi English LED alarm relay indications LED alarm relay operation table Start up sequence (normally closed) (normally open) Pump status Condensate level Default operation Peripheral Mode Not powered N/A NC NC COM COM NC NC COM COM Powered Below alarm level NC NC COM COM NC NC COM COM Powered Alarm-activated NC NC COM COM NC NC COM COM ❋ Alarm relay operation is user configurable see page 11 ❋ LED indications in operation Or No power Pump is miswired or no
English Instruction manual Combi ON 1 ON Factory default 1 2 low up to 18K Btu/h (5.3kW) 2 ON ON ON 1 2 1 2 1 2 medium low up to 42K Btu/h (12kW) medium high up to 72K Btu/h (21.1kW) high up to 120K Btu/h (35kW) Ratings for air conditioning units The rating of the condensate pump has to be adjusted according to the power of the conditioning unit. Transport and storage Transport Inspect the Combi for any potential transportation damage.
Instruction manual Combi English Horizontal installation 1a Vertical installation 1b Leave silicone plug in water sensor. Remove plug and install vent tube.
English 2b Instruction manual Combi Vertical installation 1 12 8 11
Instruction manual Combi English 3 12 11 9
English Instruction manual Combi 4 Examples are for reference only. 11 10 12 WARNING: Disconnect all electrical power before starting installation, maintenance, or service work. INPUT POWER: 100-240V, 50/60Hz, 2.5A (Max) Installations must only be carried out by qualified personnel. The alarm relay fuse must be rated for the specific application and of the HRC type, 5 x 20mm 250 VAC, 10A (Max) Plug connections have to be completely dry.
Instruction manual Combi English Below are examples of how REFCO pumps can be installed. For reference only.
English Instruction manual Combi Below are examples of how REFCO pumps can be installed. For reference only.
Instruction manual Combi English 5 1 1 10 6 14 1 2 3 11 12 1 3 2 Power cable 11 must not be entered with a tensile load. Alarm cable 12 and power cable must be completely pressed into the jack. Only use the original power cable 11 and alarm cable 12 .
English 7a Instruction manual Combi Horizontal installation 1 2 1/4˝ I.D.
Instruction manual Combi Vertical installation 1 2 1/4˝I.D.
English Instruction manual Combi Maintenance Water filter maintenance Regular cleaning / replacement of the Combi water filter will help to prolong the life of the pump. The sole purpose of the water filter is to prevent foreign debris from entering the pump itself. The time period between filter service can only be determined from the specific environment in which the pump is installed. We recommend cleaning or replacing the water filter a minimum of every 12 months.
Instruction manual Combi English Troubleshooting Fault Correction No LED lights Check for incoming voltage. The blue and brown wires are for power. Pump runs constantly Check filter placement. The water filter should not touch the digital sensor. Check the digital sensor for dirt, mold or debris. Clean with water. Check all tubing connections and ensure they are firmly pressed on the connection barbs and secured using cable ties. Check the entire drain line for clogs, kinks or the tube being pinched.
English Instruction manual Combi Replacement parts and accessories HSG-4065/4 Stop-Siphon Device, 4 pcs. Part No 3004065 FIL-4063/4 Filter, 4 pcs. Part No 3004063 FUS-4050/10 Fuses 5x20 10A, 10 pcs. Part No 3004050 KIT-4087 Star tube with Stop-Siphon device Part No 3004087 PVC-TUBE Plastic tube 6 mm (1⁄4”), minimum 30 meters Part No 4679160 Appendix Corrected flow based on installation L/Hr. 1/4” (6mm) discharge tube @ full power A B Suction (lift) Discharge (Rise) m 0.0 m 1.0 m (3.3 Ft) 2.
Instruction manual Combi English 19