Technical data

EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
RedMax-S-Y_en
V01 – 4-Feb-2015
RedMax-...-Y RedMax-...-YF
Special options ... -CTS ... -VAS
Technical data RedMax- 5.10 -Y RedMax- 15.30 -Y RedMax- 5.10 -YF RedMax- 15 -YF
Approbations Special solutions and accessories
...-CTS Types in aluminium housing with C5-M finish, parts nickel-plated
...-VAS Types in stainless steel housing, parts nickel-plated
RedBox-Y/S... Terminal boxes for zone 2, 22
MKK-S Mounting bracket for boxes type ...Box-... directly on actuator
RedSwitch 2 external aux. switches, adjustable for zone 2, 22
HV-S... Comfortable manual override for...Max actuators size S
KB-S Clamp for damper shafts Ø 10...20 mm and
10...16 mm
AR-12-xx Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts
Kit-S8 Cable glands nickel-plated
Adaptions for dampers and valves on request
Torque motor (min.) 5 / 10 Nm selectable on site 15 / 30 Nm selectable on site 5 / 10 Nm selectable on site 15 Nm
Torque spring (F) – – min. 10 Nm min. 15 Nm
Dimension of external torque Above mentioned torques are min. torques in blocked position, external torque should be max. 80 % of max. actuator torque but min. 3 Nm
Supply voltage / frequency 24...240 VAC/DC, ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see
Extra information (in acc. with voltage, I
start
>> I
rated
), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 7,5 / 15 / 30 / 60 / 120 s/90° selectable on site
Motor Brushless DC motor
Spring return (F) – – spring return in the event of loss of power
Spring return running time (F) – – spring return in ~ 3 or 10 s/90°, selectable on site
3 sec. mode – spring return – – in acc. with external torque ~ 3 to 4 s/90° angle of rotation
Safety operations at 10 sec. min. 10,000 in acc. with construction of damper and ambient
at 3 sec. min. 1,000 in acc. with construction of damper and ambient
Response time spring return up to 1 sec. after power failure
Control mode Y 3-pos., 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site. Galvanic separation between supply and Y-signal
Feedback signal U 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site, both signals are available at the same time
Resistance of Y and U signals Input signal: Y
U
0...10 VDC at 10 k, Y
I
4...20 mA at 100 . Feedback signal: U
U
0...10 VDC at 2.000...∞ Ω, U
I
4...20 mA at 0...800
Reverse function Bridge between wiring 3 and 4 (signal wise) gets a reverse function of Y and U
Compulsion control In modulation mode an On-off compulsion control can be performed by external connection/wiring independently from the modulating signal
Adjustment of Y and U In case of external mechanical limitation of the angle of rotation, it is possible to perform an adjustment drive started by pushing the button (T)
Axle of the actuator Double square 12 × 12 mm, direct coupling, 100 % overload protected and self locking up to 15 Nm
Electrical connection 2 cable glands ~ 1 m each, wire cross section 0.5 mm², equipotential bonding 4 mm².
Connections in hazardous areas require a terminal box!
Diameter of cable ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm ~ Ø 7.4 mm each ~ Ø 7.4 mm each
Cable gland M16 × 1.5 mm standard cable and wire entries
Manual override Use delivered socket wrench, max. 4 Nm
Integral heater Integral, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die cast housing, painted. Optional with seawater resistant C5-M finish (...-CTS) or housing in stainless steel DIN EN 1.4581 /
V4A / UNS-J92900 / similar AISI 316 Cb (...-VAS)
Dimensions L × W × H = 210 × 95 × 80 mm, for diagrams see
Extra information
Weight ~ 3,5 kg aluminium housing, stainless steel ~ 7 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+40 °C at T6 and −40…+50 °C at T5
Humidity 0...90 % rH, non condensing
Operating 7,5 sec. motor run time at 24 V 50 % ED S3 (ED = duty cycle)
15 sec. motor run time at 15 / 30 / 60 / 120 s 100 % of ED is permitted
Accuracy electrically ~ 100 steps
Self adjustment Before initial operation you need to start the self adjustment mode for „gentle blockade“ and adjustment of rotation angle
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 5.0 / 5.1 / 5.2 / 5.3
Scope of delivery Actuator with 2 × 1 m cable, 4 screws M4 × 100 mm, 4 nuts M4, Allen key for simple manual override
Parameter at delivery 5 Nm, 30 s/90° 15 Nm, 30 s/90° 5 Nm, 30 s/90° 15 Nm, 30 s/90°
ATEX tested PTB 04 ATEX 2106
IECEx tested IECEx PTB 08.0059
In acc. with ATEX 94/9/EC
Approval for gas II 3 (1) G Ex nC [ia] IIC T6/T5 zone 2
II 3 G Ex nC II T6/ T5
Approval for dust II 3 D Ex tD A22 IP66 T80 °C zone 22
Identification CE No. 0158
EMC 2004/108/EC
Low voltage 2006/95/EC
IP-Protection IP66 in acc. with EN 60529
2 / 4