Technical data

www.schischek.com
Technical data RedMax-5.10 RedMax-15.30 RedMax-5.10-F RedMax-15-F
Accessories or special solutions - size S
Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email info@schischek.com
RedMax-5.10 RedMax-15.30 RedMax-5.10-F RedMax-15-F
Special makes RedMax-..-S/SF
RedMax-..-VA/-CT
EXPLOSIONPROOF
Certification PTB 04 ATEX 2106
ATEX Directive 94/9/EG (ATEX)
Approval for gas II3G EEx nC II T6 II3(1)G EEx [ia] IIC gas, mist, vapour,
zone 2
Approval for dust II3D IP66 T80°C dust, zone 22
Identification CE Nr. 0158
EMC EMC-directive 89/336/EG
Low voltage Low-voltage directive 72/23/EG
IP-Protection IP 66
Potential compensation external PA-terminal, 4 mm²
Torque motor 5 / 10 Nm selectable on site 15 / 30 Nm selectable on site 5 / 10 Nm selectable on site 15 Nm
Torque spring return (F) without F without F min. 10 Nm min. 15 Nm
Dimension of external torque above mentioned torques are min. torques in blocked position, external torque should be max. 80 % of max. actuator torque but min. 3 Nm
Supply voltage/Frequency
24...230 VAC/DC, + 15 % / - 20% , self adaptable, Frequency 50...60 Hz +/- 20 %
Dimension
max. starting currents see table (in acc. with voltage, I start >> I rated), max. 20 W blocking position, approx. 16 W for heater
Protection class class I (grounded)
Angle of rotation and indication 95°, incl. ~ 5° pre-tention, mechanical value indication
Working direction selectable by left/right mounting to the damper/valve shaft
Motor running time 3 / 15 / 30 / 60 / 120 sec. at 90° selectable on site
3 sec. mode - motor In acc. with the supply voltage rand external torque 3 to 4 sec at 90° angle of rotation
Motor
brushless DC Motor
Spring return (F) without F without F spring return in the event of loss of power
Spring return running time (F) without F without F
spring return in 3 sec., or 10 sec. at 90°, selectable on site
3 sec. mode - spring return without F without F in acc. with external torque 3 to 4 sec. at 90° angle of rotation
Safety operations at 10 sec (F) without F without F min. 10.000 in acc. with construction of damper and ambient
Safety operations at 3 sec (F) without F without F min. 1.000 in acc. with construction of damper and ambient
Response time spring return up to 1 sec. after power failure
Control mode On-off and 3-pos in acc. with wiring, selectable on site
Axle of the actuator
double squared 12 x 12 mm, direct coupling, 100 % overload protected
Electrical connection cable, ~1 m, diameter of wires 0,5 mm², for connection inside hazardous areas an EEx-e terminal box is required!
Diameter of cable ~ Æ
7,1 mm ~ Æ 7,1 mm ~ Æ 7,4 mm ~ Æ 7,4 mm
Cable gland M16 x 1,5 standard
Manual override
Manual override only if supply voltage is cut, use delivered socket wrench, slow motion, enogh torque/force is required
Attention: with manual operation of actuators with spring return danger of injury exists, with release/let go the hexagonal spanner.
Integral heater integral heater, controlled, for ambient temperature down to - 40°C
Housing material Aluminium die cast housing, painted (optional in stainless steel version AISI 316 - type ..-VAS, amercoat painting type ..-CTS)
Dimensions l x w x h 210 x 95 x 80 mm, for diagramm see extra information ME
Weight
~ 3,5 Kg Aluminium housing (stainless steel ~ 7 Kg)
Ambients storage temp. - 40..+ 70°C, working temperature - 40..+ 40°C at T6 and - 40...+ 50°C at T5, humidity in acc. with EN 60335-1
Operation mode at
runningtime motor 3 sec. at 3 sec. 10 % ED, max. 1 on-off cycle per minute (must be guaranteed by control system)
Operation mode ex
runningtime motor 15 sec. at 15/30/60/120 sec. 100 % ED
Self adjustment if you select 3 sec. and 15 sec. mode for motor you need to start the self adjustment mode.
Maintenance maintenance free, maintenace must be complied with regional standards, rules and regulations
Wiring diagrams (SB) SB 1.0 SB 1.0 SB 2.0 SB 2.0
Delivery 1 actuator, 1 m cable, double squared shaft connection 12x12 mm, 4 screws M 4 x 100, 4 nuts M 4
socket wrench for simple manual override
Parameter at delivery 5 Nm, 30 sec./90° 15 Nm, 30 sec./90° 5 Nm, 30 sec./90° 15 Nm, 30 sec./90°
Explosion proof RedMax actuators - size S
RedMax-...-S 2
internal, potential free aux. switches at 5°/85°, 24V/3A, 230V/0,25A, SB 3.5
RedMax-.-VASabove listed types in stainless steel version, housing AISI 316.
RedMax-.-CTSabove listed types in Al-housing with amercoat painting, parts nickel-plated
RedBox-... Terminal boxes for zone 2, 22.
MKK-S mounting bracket for Terminal boxes type RedBox-... direct on actuator
RedSwitch 2 external aux. switches, 2 x EPU, adjustable, for zone 2, 22
KB-S clutch for damper shafts Æ 10...20 mm and 10...16 mm.
HV-S comfortable manual override for RedMax actuators size S
Adaptations various adaptations for dampers/valves on request
AR-12-xx Reduction of square damper connection from 12 mm to 11, 10, 9, 8