Manual
6
1 PRODUCT FUNCTION
1.4 Turn On/Off Thresholds
Input 12V Vehicle Input 24V Vehicle Input Solar
Input Trigger
Settings
Standard
Low
Voltage
Standard
Low
Voltage
N/A
Input
Open Circuit
Low voltage
conditions *
1
Turn ON
ABOVE
13.2V 12.0V 26.4V 24.0V 9.0V
Turn OFF
BELOW
12.7V 11.9V 25.4V 23.8V 9.0V
Input
Loaded Low
voltage
conditions*
2
Turn OFF instantly
BELOW
8.0V 16.0V 9.0V
Turn OFF after 20s
BELOW
9.0V 18.0V N/A
Input
Over voltage
shutdown
Turn ON
BELOW
15.5V 32V
Turn OFF instantly
ABOVE
16.0V 32.5V 33.0V
Turn OFF after 20s
ABOVE
15.6V 32.1V N/A
Output
Under voltage
shutdown *
1
Shutdown if Output Battery < 4V
There is a maximum 20 second delay before the charger will produce an output
any time a source is introduced into the system, this allows the unit to provide
optimum input sharing and effective battery isolation.
1.5 Error Codes
In the event of a fault with the unit installation, either battery or solar panel, the
LEDs on the unit will fl ash to indicate the fault type. Flashing sequences and the
LEDs that display them are described in the table below.
LED State Description Display LEDs
1 fl ash (1 fl ash, 3.5s off) Internal Hardware Fault ALL
2 fl ash (2 fl ashes, 3.5s off) Unit under temp fault ALL
3 fl ash (3 fl ashes, 3.5s off) Unit over temp fault ALL
4 fl ash (4 fl ashes, 3.5s off) Output Battery Fault (Volts too high) ALL
5 fl ash (5 fl ashes, 3.5s off) Input under voltage (Vehicle or Solar) Vehicle or Solar LED
6 fl ash (6 fl ashes, 3.5s off) Input over voltage (Vehicleor Solar) ALL
*
1
Tested every 100 Seconds.
*
2
Constantly tested.