Instruction Manual

Display Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
tYPE Input type tc-t - Type T TC
tc-E -Type E TC
tc-J - Type J TC
tc-k - Type K TC
tc-r - Type R TC
tc-S - Type S TC
tc-B - Type B TC
tc-N - Type N TC
LIN - Linear mV display
If changed, check PID
settings and input select
jumper position. (jumper in
TC position)
r385 - 385 curve RTD
r392 - 392 curve RTD
rLIN - Linear ohms display
(tc-J)
(jumper in RTD position)
SCAL Temperature
scale
°F/°C
(°F)
If scale is changed, all
parameters must be
checked.
dCPt Temperature
resolution
0 or 0.0
(0)
If resolution changed, all
parameters must be
checked.
FLtr Digital filtering for
input signal
0to3
(1)
Increase number for more
filtering effect.
SPAN Input signal slope
(correction factor)
0.001 to 9.999
(1.000)
Normally set to 1.000
SHFt Input signal offset
(correction shift)
-999 to 9999
1 or 0.1 degree
(0)
Normally set to 0
SPLO Lower limit
setpoint range
-999 to 9999
1 or 0.1 degree
(0)
Set low limit below high
limit.
SPHI Upper limit
setpoint range
-999 to 9999
1 or 0.1 degree
(9999)
Set high limit above low
limit.
Display Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
SPrP Setpoint ramp rate 0.0 to 999.9
degrees/minute
(0.0)
0.0 is off (no auto
ramping)
(Not related to profile
operation.)
InPt User input PLOC - Program disable
ILOC - Integral action
on/off
trnF - Auto/manual transfer
SPrP - Ramp rate on/off
ALrS - Reset alarm
output(s)
Prnt - Print request
CP - Control point load
P1rH - Run/pause a profile
or start profile 1
P1rS - Profile 1 stop/restart
(PLOC)
-49-
QUICK REFERENCE TABLE: CONFIGURATION INPUT MODULE 1 (1-IN)