7.4 module 4 - AlArm pArAmeterS (4-AL) (optionAl)
ACt1 rSt1
Lit1
Stb1
AL-1
ACt2 Lit2
ALARM 1
ACTION
ALARM 1
ANNUNCIATOR
ALARM 1
RESET ANNUNCIATOR
ALARM 2ALARM 2
ACTION
4-AL
CNFP
AHYS
HYSTERESIS
ALARM 1 & 2ALARM 1
VALUE RESET
ALARM 2
STANDBY
ALARM 2
rSt2 stb2
MODE
STANDBY
ALARM 1
MODE
AL-2
ALARM 2
VALUE
PARAMETER MENU
OFF
ON
AL + ½Hys
AL
AL - ½Hys
OFF
Absolute High Acting (Balanced Hys)
Hys
TRIGGER POINTS
ALARM
STATE
ALARM
STATE
OFF ON
Hys
SP + AL
SP
OFF
TRIGGER POINTS
Deviation High Acting (AL > 0)
ALARM
STATE
Hys
SP - AL
SP
SP + AL
Hys
TRIGGER POINTS
ON OFF OFFON ON
Band Inside Acting
OFF ON
AL + ½Hys
AL
AL - ½Hys
OFF
Absolute Low Acting (Balanced Hys)
TRIGGER POINTS
Hys
ALARM
STATE
ALARM
STATE
OFFON
Hys
SP - AL
SP
OFF
TRIGGER POINTS
Deviation Low Acting (AL > 0)
ALARM
STATE
OFF ON
Hys
AL
AL - Hys
OFF
TRIGGER POINTS
Absolute High Acting (Unbalanced Hys)
ALARM
STATE
OFF ON
Hys
AL + Hys
AL
OFF
TRIGGER POINTS
Absolute Low Acting (Unbalanced Hys)
ALARM
STATE
ON OFF
Hys
SP + (-AL)
SP
ON
TRIGGER POINTS
Deviation High Acting (AL< 0)
ALARM
STATE
ON
Hys
SP - AL
SP
OFF
SP + AL
ON
Hys
OFF OFF
TRIGGER POINTS
Band Outside Acting
ALARM ACTION FIGURES
Note: Hys in the above figures refers to the Alarm Hysteresis.
AVAILABLE ALARM ACTIONS

None
No action, the remaining Alarm
parameters are not available.
I
Absolute High
(balanced hysteresis)
The alarm energizes when the Process
Value exceeds the alarm value + 1/2
the hysteresis value.

Absolute Low
(balanced hysteresis)
The alarm energizes when the Process
Value falls below the alarm value -1/2
the hysteresis value.
I
Absolute High
(unbalanced hysteresis)
The alarm energizes when the Process
Value exceeds the alarm value.

Absolute Low
(unbalanced hysteresis)
The alarm energizes when the Process
Value falls below the alarm value.
I
Deviation High
Alarm 1 and 2 value tracks the
Setpoint value

Deviation Low
Alarm 1 and 2 value tracks the
Setpoint value
I
Band Acting
(inside)
Alarm 1 and 2 value tracks the
Setpoint value

Band Acting
(outside)
Alarm 1 and 2 value tracks the
Setpoint value

Heat (A1 Analog
models only)
If heating is selected, the remaining
Alarm 1 parameters are not available.

Cool
(A2 only)
If cooling is selected, the remaining
Alarm 2 parameters are not available.