User Manual
1919
6.6 MODULE 6 - SETPOINT (ALARM) PARAMETERS ()
Output
Logic
Setpoint
Annunciator
Setpoint
Value
Setpoint
Assignment
Setpoint
Action
Power-up
State
Boundary
Type
Setpoint
Tracking
SPSEL
Setpoint
Select
PAR
6-SPt
OUt-n
ASN-n ACt-n SUP-n SP-n trC-n tYP-n
Pro
LIt-n
tON-n
On Time
Delay
HYS-n
Setpoint
Hysteresis
Stb-n
Standby
Operation
PAR
tOFF-n
Off Time
Delay
Output Reset
when SPn+1
Activates
AUtO-n
Totalizer
Auto Reset
tOUt-n
Time-out
Value
Output Reset
when Display
Resets
rSd-n rSAS-n
Output Reset
when SPn+1
Deactivates
rSAE-n
PARAMETER MENU
Module 6 is the programming for the setpoint (alarms) output parameters. To have setpoint outputs, a setpoint Plug-in card needs to
be installed into the PAX (see Ordering Information). Depending on the card installed, there will be two or four setpoint outputs
available. For maximum input frequency, unused Setpoints should be configured for action.
The Setpoint Assignment and the Setpoint Action determine certain setpoint parameter availability. The chart below illustrates this.
PARAMETER
DESCRIPTION
RATE ASSIGNMENT TOTALIZER ASSIGNMENT
TIMED OUT
BOUNDARY
LATCH
TIMED OUT
BOUNDARY *
LATCH
Setpoint Output Logic Yes Yes Yes Yes Yes Yes
Setpoint Annunciator Yes Yes Yes Yes Yes Yes
Setpoint Power-Up State No No Yes No No Yes
Setpoint Value Yes Yes Yes Yes Yes Yes
Setpoint Tracking Yes Yes Yes Yes Yes Yes
Setpoint Boundary Type Yes Yes Yes No Yes No
Setpoint Standby Operation Yes Yes Yes No Yes No
Setpoint Hysteresis No Yes No No No No
Setpoint Off Delay No Yes No No No No
Setpoint On Delay Yes Yes Yes No No No
Setpoint Time Out Yes No No Yes No No
Totalizer Auto Reset No No No Yes No Yes
Reset With Display Reset No No No Yes No Yes
Reset When Spn+1 Activates No No No Yes No Yes
Reset When Spn+1 Deactivates
No No No Yes No Yes
* BOUNDARY is the only Setpoint Action available for setpoints assigned to Totalizer C.
SETPOINT PARAMETER AVAILABILITY
SETPOINT SELECT
Select a setpoint (alarm output) to open the remaining module menu. (The
“” in the following parameters will reflect the chosen setpoint number.) After
the chosen setpoint is programmed, the display will default to
. Select
the next setpoint to be programmed and continue the sequence for each setpoint.
Pressing PAR at
will exit Module 6.
SETPOINT OUTPUT LOGIC
Normal () turns the output “on” when activated and “off” when
deactivated. Reverse () turns the output “off” when activated and “on” when
deactivated.
SETPOINT ANNUNCIATORS
disables the display of the setpoint annunciator. Normal () displays
the corresponding setpoint annunciator of an “on” alarm output. Reverse ()
displays the corresponding setpoint annunciator of an “off” alarm output.
flashes the display and the corresponding setpoint annunciator of an
“on” alarm output.
SETPOINT ASSIGNMENT
Select the display to which the setpoint is assigned.










