Automation Tab
FloatingInputsMapI/O:ThisoptionprovidesconfigurationofMappingFloatInputI/O’sReg/IndextoDNP
pointsforgeneratingeventsbasedonconfiguredDeadBandandClassAssignmentswhenthestatusofanyFloat
InputI/O’schange s.
DefaultDeadBandandClassAssignmentsareappliedtoalltheReg/IndexdefinedbyHighestRegisterAddressexceptReg/
IndexentriesthataredefinedinExceptionDeadBandandClassAssignmentsTable.
ConfigureDNPPoints:IfoptionissettoNo,thennoFloatingInputsaremappedasDNPpoints.IfsettoYes,
theHigh
estRegisterAddressfieldisshowntoenteraHighestRegisterAddressvalue.
HighestRegisterAddress(Required):ThisfieldisusedtoshoworsetthehighestregisteraddresstomapDNPpoints.
EnterDefaultDeadBandValue:Valuesoutsidethisdeadbandgenerateevents.Thedeadbandparametersetshow
event
dataisgeneratedbyyourmoduleasaDNPslavedevice.
Forexample:TheAnalogInputdeadbandbeingsettoavalueof1000willreportallofthepointsasbeingclass3data(asset
bythe“AnalogInputclass”parameterbeingsetto3)anditwillgenerateaneventeverytimeananaloginputchangesbya
value
of1000ormore.ThisAnalogInputdeadbandcanbesettoanyvaluebetween0to32767(generateaneventwhenthe
valuechangesby32767).
DefaultObject31‐FrozenAnalogInput:ThisfieldisactivatedonbothLevels2and2+.ItsusedtodetermineifaDNP
pointwillgenerateevents.IncaseaDNPpointgenerate sevents(Object2BinaryChangeEvents)thenitshouldbe
associatedtoaclass(Class1,Class2or
Class3),otherwiseitshouldbeassociatedtoNone.BydefaultallDNPPoints
don’tgenerateevents,thisfeatureshouldbemodifiedbytheuser.