Manual

Table Of Contents
Software User Guide 117
Automation Tab
DeviceName:Nameoftheserialdevice.Validvalues:ttys1(RS232),ttys5(RS485)
BaudRate:Baudratefortheserialdevice.Supportedbaudratesare:300,600,1200,2400,4800,9600,19200and
38400.
DataBits:Numberofdatabits.Supporteddatabitsare7and8.
Parity:Parityforserial
device.Supportedparitiesare:none,even,odd,markandspace.
FlowControl:Flowcontrolforserialdevice.Supportedflowcontrolsare:none,hardware,xon/xoff,halfduplex,full
duplex.
StopBits:Stopbitsforserialdevice.Supportedstopbitsare1and2.
Protocol:Protocolbeingusedonserialdevice.Supportedprotocols
are:DNP3,Mod b usMasterASCII,ModbusMas
terRTU,ModbusSlaveASCII,ModbusSlaveRTU,ModbusMasterRTUFwdandModbusASCIIFwd.
FloatWordOrder:Controlstheswappingofwordswithinfloats.IgnoredifusingDanielmode.Thisisneededforcon
figuringtheserialslaveapplication.Supportedordersare
LSWandMSW.
LongWordOrder:Controlstheswappingofwordswithinlongs.IgnoredifusingDanielmode.Thisisneededforcon
figuringtheserialslaveapplication.SupportedordersareLSWandMSW.
EnableDanielMode:UseDanielmodeextensionswhendealingwithlongsandfloats.Thisisneededfor
configuring
theserialslaveapplication.
ClickontheFinishbuttontopopulatetheSerialPortsTableProperties.
Todeleteanaddress,selectitinthetableandclickontheDeletebutton.Toeditanexistingrule,selectitinthe
tableandclickontheEditbutton.
Clickonthe
“Savebuttonforchangestobesavedwithoutactivatingtheinterfaceuntilyoureboottheunit,the
Apply ” buttonwillsaveyoursettingsandapplythemimmediately.Toreverttothepreviousdefaults,clickonthe
“Revertbutton.
3.6.3 Mod bus