Manual
1
  ETHERNET GATEWAY FOR RED LION PANEL METERS
  PROGRAMMABLE VIA CRIMSON SOFTWARE
  USB PROGRAMMING PORT
  EXTENSIVE ETHERNET DRIVER LIST ALLOWS EASY DATA 
MAPPING TO PLCS, PCS, AND SCADA SYSTEMS
  10 BASE-T/100 BASE-TX ETHERNET
GENERAL DESCRIPTION
The ICM8 is designed to act as an ethernet gateway offering multiple 
protocol conversion for Red Lion panel meters. With two serial ports (one 
RS232 and one RS485) and a 10 Base-T/100 Ethernet Port, the unit performs 
protocol conversion, allowing Red Lion panel meters to communicate 
seamlessly to the ethernet network. Programming the unit can be accomplished 
via the RS232 or the USB Port using Crimson Software. It is important to note 
that this device is designed to function with Red Lion panel meters and will not 
offer protocol conversion if a Red Lion Product is not connected to at least one 
of the serial ports.
The ICM8’S DIN rail mounting saves time and panel space and snaps easily 
onto standard top hat (T) profile DIN rail.
SOFTWARE
The ICM8 is programmed with Windows
®
 compatible Crimson software. 
The software is an easy to use graphical interface which can be purchased as part 
of a kit that includes a manual and cables, or downloaded free of charge from 
www.redlion.net.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the 
manual or on equipment must be observed to ensure personal safety and to 
prevent damage to either the instrument or equipment connected to it. If 
equipment is used in a manner not specified by the manufacturer, the protection 
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER: 24 VDC ± 10% 200 mA max. Must use a Class 2 or SELV rated 
power supply.
2. COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using Type B 
connection.
Serial Ports: Format and Baud Rates for each port are individually software 
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS485 port via RJ11
Ethernet Port: 10 BASE-T / 100 BASE-TX
3. LEDs:
STS – Status LED indicates condition of ICM8.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM: 2 Mbytes
MODEL ICM8 – ETHERNET GATEWAY
Bulletin No. ICM8-C
Drawing No. LP0642
Released 12/11
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to 
installation and operation of the unit.
4.15 (105.4)
5.30
(134.7)
1.75 (44.5)
DIMENSIONS In inches (mm)