APPENDIX “D” - GEMINI FUNCTION COMMAND CODE SUMMARY (Con’t)
–46–
CODE MODE DESCRIPTION COMMENTS
51 RESET MODES
- (+) Maintained Unit will remain reset as long as reset is activated.
- (-) Momentary Unit will reset instantly and will start counting again even if reset is still
activated.*
+/-1 Manual to zero Automatically selected when Rate or Boundary [54 6],is programmed,
all others are locked out.
+/-2 Manual to Preset **
+/-3 Auto to Zero after Output Time Delay ** Output activates at Preset **
+/-4 Auto to Preset after Output Time Delay ** Output activates at zero. **
+/-5 Auto to Zero at Preset **
+/-6 Auto to Preset at Zero **
52 OUTPUT 1 TERMINATION
- (+) Normal Phase Output normally “OFF”, turns “ON” at preset.
- (-) Reverse Phase* Output normally “ON”, turns “OFF” at preset.*
+/-1 Terminate at Output 2 Start (Gemini 2000 Only)
+/-2 Terminate at Output 2 End (Gemini 2000 Only)
+/-3 Terminate at Manual Reset
+/-4 Terminate at Manual Reset End
+/-5 Terminate after Output 1 Time Delay
+/-6 Boundary
53 NA OUTPUT 1 TIME DELAY Range 0.01 to 599.99 sec.
54 OUTPUT 2 TERMINATION (Gemini 2000 Only)
- (+) Normal Phase Output normally “OFF”, turns “ON” at preset.
- (-) Reverse Phase* Output normally “ON”, turns “OFF” at preset.*
+/-1 Terminate at Output 1 Start
+/-2 Terminate at Output 1 End
+/-3 Terminate at Manual Reset
+/-4 Terminate at Manual Reset End
*Polarity sign is displayed in front of the identifier, a (-) sign is displayed, a (+) sign is not.
** For the Gemini 2000, all reset to preset modes reset to preset 2 and Output refers to Output 2.