Manual
RS422/485 COMMS PORT
The G306 has one RS422/485 port. This port can be configured to act as
either RS422 or RS485.
Note: All Red Lion devices connect A to A and B to B, except for Paradigm
devices. Refer to www.redlion.net for additional information.
5
RS232 PORTS
The G306 has two RS232 ports. There is the PGM port and the COMMS
port. Although only one of these ports can be used for programming, both ports
can be used for communications with a PLC.
The RS232 ports can be used for either master or slave protocols with any
G306 configuration.
Examples of RS232 communications could involve another Red Lion
product or a PC. By using a cable with RJ12 ends on it, and a twist in the cable,
RS232 communications with another G3 product or the Modular Controller can
be established. Red Lion part numbers for cables with a twist in them are
CBLPROG0
1
, CBLRLC01
2
, or CBLRC02
3
.
Connections
G3: RJ12 Name PC: DB9 Name
4 COMM 1 DCD
5 Tx 2 Rx
2 Rx 3 Tx
N/C 4 DTR
3 COM 5 GND
N/C 6 DSR
1 CTS 7 RTS
6 RTS 8 CTS
N/C 9 RI
OFF 4 WIRE/ ON 2 WIRE
OFF 4 WIRE/ ON 2 WIRE
*
*
*
*
*
*
*
*
*
*
9
PULL UP
PULL DOWN
115200 BAUD
57600 BAUD
38400 BAUD
19200 BAUD
9600 BAUD
2
1
5
3
4
7
8
6
OFF DCE/ ON DTE
OFF DCE/ ON DTE
OFF DTE/ ON DCE
OFF 422/ ON 485
OFF 422/ ON 485
OFF DTE/ ON DCE
120 Ω TERMINATION
5
NC
10
1
3
2
4
6
7
ON
ON
CBLPROG0
ICM5
CONNECTING A G306 OPERATOR
INTERFACE TO AN ICM5
*
Application Dependent
ICM5 DIP Switch Settings
Examples of RS485 2-Wire Connections
G3 to Red Lion RJ11 (CBLRLC00)
DLC, IAMS, ITMS, PAXCDC4C
A+4TxA2
B-5TxB1
COM3COM6
TxEN2TxEN5
Name
RLC: RJ11Name
G3: RJ45
Connections
G3 to Modular Controller (CBLRLC05)
TxA8TxA8
TxB7TxB7
COM6COM6
TxEN5TxEN5
RxA
TxA
3,2
2,3
RxA
TxA
3,2
2,3
RxB4,1RxB4,1
TxB1,4TxB1,4
NameModular ControllerNameG3
Connections
1
CBLPROG0 can also be used to communicate with either a PC or an ICM5.
2
DB9 adapter not included, 1 foot long.
3
DB9 adapter not included, 10 feet long.
DH485 COMMUNICATIONS
The G306’s RS422/485 COMMS port can also be used for Allen Bradley
DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect this port to Allen
Bradley equipment. A cable and wiring diagram are available from Red Lion.
G3 to AB SLC 500 (CBLAB003)
24V-TxA3, 8
COMM-TxB4, 7
SHIELD4COMM6
TxEN5TxEN5
COMM-RxB4, 7
24V-RxA3, 8
B2TxA2
A1TxB1
NameRJ45: A-BNameRJ45: RLC
Connections
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
GND
6
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 GND
RS422/485 4-WIRE
CONNECTIONS
RS485 2-WIRE
CONNECTIONS
G3 RS232 to a PC