WIRING CONNECTIONS
The electrical connections are made via rear screw-clamp terminals located
on the back of the unit. When wiring the unit, use the label to identify the wire
position with the proper function. All conductors should meet voltage and
current ratings for each terminal. Also cabling should conform to appropriate
standards of good installation, local codes and regulations. It is recommended
that power supplied to the unit (AC or DC) be protected by a fuse or circuit
breaker. Strip the wire, leaving approximately 1/4" bare wire exposed (stranded
wires should be tinned with solder). Insert the wire into the screw-clamp
terminal and tighten down the screw until the wire is clamped tightly. Each
terminal can accept up to two #14 AWG wires.
Backlight Wiring
Optional backlight versions of the CUB4 require an external 9-28 VDC
power supply. The external supply is connected between the V+ and Common
terminals.
Warning: Lithium battery may explode if incinerated.
3 RESET
1 COM
M1406_
!
MADE IN U.S.A.
9-28 VDC 2
COUNT 4
YORK, PA.
CUB4
Backlight Power Supply
(MLPS)
_
+
Current Sinking Output
Switch position is application dependent.
SRC
LO FREQ
KEY ENKEY DIS
HI FREQ
2
1
SNK
ON
*
3
Reset
Com
CNT
9-28VDC
3
1
2
4
Current Sourcing Output
SRC
LO FREQ
KEY ENKEY DIS
HI FREQ
2
1
SNK
ON
*
3
+V
Reset
Com
CNT
9-28VDC
3
1
2
4
Logic Output
SRC
LO FREQ
KEY ENKEY DIS
HI FREQ
2
1
SNK
ON
*
3
Reset
Com
CNT
9-28VDC
3
1
2
4
Switch/Contact Sinking Output
KEY EN
LO FREQ
SRCSNK
HI FREQ
KEY DIS
1
ON
3
2
*
Reset
Com
CNT
9-28VDC
3
1
2
4
Switch/Contact Sourcing Output
SRC
LO FREQ
KEY ENKEY DIS
HI FREQ
2
1
SNK
ON
*
3
+V
Reset
Com
CNT
9-28VDC
3
1
2
4
COUNT INPUT WIRING