Technical Specification
HP NetServer LC 2000/2000r Input Power
Input Voltage and
Frequency:
100-240 VAC ± 10%; 50/60 Hz
Maximum inrush
current:
8 AMPs peak (for 1 power supply) 120 VAC
or 32 AMPs peak (2 power supplies)
16 AMPs peak (for 1 power supply) 240 VAC
or 32 AMPs peak (2 power supplies)
Delayed action circuit
breaker recommended:
North America: a 20 A minimum delayed action circuit recommended for
each 16 A power distribution unit (PDU) that is connected to an HP
NetServer LC 2000/2000r.
Europe (single server in a rack): Use a 16 A-minimum circuit with one
IEC MCB C-type breaker for each 16-Amp PDU.
Europe (multiple servers in a rack): Use a 16-amp-minimum circuit with
one IEC MCB D-type breaker for each 16 A PDU.
NOTE Some local codes do not allow 16-amp service for a 16-amp device. Consult a
qualified electrician or local regulatory authority before beginning electrical site
preparation.