Panel Install manual
Table Of Contents
- Fig. 5: Clamping of REC Alpha Series panels using a short support
- Fig. 6: Clamping of REC Alpha 72 Series panels with support parallel to short side of the module
- Fig. 7: Clamping of REC Alpha 72 Series panels using a short support
- Fig. 8: Mounting holes: REC Alpha Series
- Fig. 9: Mounting holes: REC Alpha 72 Series
- Fig. 10: Device specifications for mounting holes
- Fig. 11: Mounting hole installation example
- Fig. 12: Drainage and grounding holes
- Fig. 13: Grounding lug dimensions and fastening torque
- Fig. 14: Connector mating matrix
- Fig. 15: Minimum cable bend radius
- Fig. 17: Panel dimensions: REC Alpha Black Series
- Fig. 18: Panel dimensions: REC Alpha 72 Series
- Fig. 19: REC Alpha Series MLPE device installation zones
- Fig. 20: REC Alpha 72 Series MLPE device installation zones
- Irradiance (W/m²)
- Irradiance (W/m²)
- module
- module
- module
- Rel. Efficiency (%)
- Rel. Efficiency (%)
- Support length under
- Support length under
- Support length under
- Support position
- Support position
- INTRODUCTION
- SAFETY MEASURES
- PANEL HANDLING
- CHOOSING AN INSTALLATION LOCATION
- ELECTRICAL INSTALLATION
- MECHANICAL INSTALLATION
- PANEL INSTALLATION
- CONNECTIONS AND CONNECTORS
- CABLE MANAGEMENT
- PANEL MAINTENANCE
- RECYCLING
- DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT
- PANEL CHARACTERISTICS
- ANNEX 1: INSTALLATIONS ON WATER PLATFORMS
- ANNEX 2: INSTALLATIONS USING MODULE LEVEL POWER ELECTRONICS
- DOCUMENT HISTORY
- Fig. 1: Clamp specifications
- Fig. 2: Panel quarter divisions
- Fig. 3: Clamping of REC TwinPeak 4 Series panels with rails parallel to short side of the panel
- Fig. 4: Clamping of REC TwinPeak 4 Series panels with rails parallel to long side of the panel
- Fig. 5: Clamping of REC TwinPeak 4 Series panels using a short support
- Fig. 6: Clamping of N-Peak panels on rails parallel to short side of module
- Fig. 7: Clamping of N-Peak panels on rails parallel to long side of module
- Fig. 8: Clamping of REC N-Peak Series panels using short rails
- Fig. 9: Clamping of REC N-Peak 2 Series panels with rails parallel to short side of the panel
- Fig. 10: Clamping of REC N-Peak 2 Series panels with rails parallel to long side of the panel
- Fig. 11: Clamping of REC N-Peak 2 Series panels using a short support
- Fig. 12: Mounting holes: REC 60-cell panels
- Fig. 13: Mounting holes: REC 72-cell panels
- Fig. 14: Device specifications for mounting holes
- Fig. 15: Mounting hole installation example
- Fig. 16: Drainage and grounding holes
- Fig. 17: Grounding lug dimensions and fastening torque
- Fig. 18: Connector mating matrix
- Fig. 19: Minimum cable bend radius
- Fig. 20: Panel dimensions: REC TwinPeak 4 Series
- Fig. 21: Panel dimensions: REC TwinPeak4 Black Series
- Fig. 22: Panel dimensions: REC N-Peak Series
- Fig. 23: Panel dimensions: REC N-Peak Black Series
- Fig. 24: Panel dimensions: REC N-Peak 2 Series
- Fig. 25: Panel dimensions: REC N-Peak 2 Black Series
- Fig. 26: REC 60-cell panels MLPE device installation zones
- Fig. 27: REC 72-cell panels MLPE device installation zones
REC Installation Manual - REC Panels - UL 6
Rev L . Ref: PMIM
ANNEX : INSTALLATIONS ON WATER PLATFORMS
The REC solar panels covered by this manual may be installed on water platform-type mounting systems (note that the certification testing of solar
panels does not include testing on these types of systems). When installing REC solar panels on fixed position (e.g., anchored) water platforms, for
example, floating pontoons, follow the instructions below specific to such applications. Failure to do so will invalidate the warranty.
INSTALLATION ENVIRONMENT
i) Installation site
• REC solar panels may only be installed on closed bodies of fresh water where water salinity does not exceed PSU ( mS/cm) at °F (°C). This
specifically excludes mounting on sea and ocean applications.
• The maximum permied wave height must not exceed m from the crest to the trough of the wave.
ii) Floating platforms
• When using a floating platform, follow the manufacturer’s instructions regarding installation, maintenance, inspection and cleaning at all times.
iii) Minimum installation height
• The minimum installation height of REC solar panels on floating platform systems is 6 in ( cm) and is defined as the height between the water
surface and the lowest edge/part of the panel during normal operation. This will help to shield the panel from direct water spray.
INSTALLATION INSTRUCTIONS
i) System installation
• All cables used for the installation must have sufficient length and slack to prevent damage due to water level changes and wave motions.
ii) Mounting panels
• Installation of REC solar panels must be in accordance with the aforementioned standard mounting instructions.
• The junction box should be oriented as far as possible from the water surface according to system design and the junction box, cables and connectors
must be protected from direct water splash.
• The installation must allow for sufficient spacing between individual panels, in order to avoid all contact as caused by the natural movement and
flexing of the floating structure.
iii) Panel protection
• In areas with high avian activity, additional bird repelling devices may be installed as long as they do not adversely affect system performance, e.g.,
shading or to the local environment etc.
• If using lightning protection equipment on the floating installation, all relevant local regulations must be respected.
MAINTENANCE
• Regularly inspect the installation to ensure all panels are securely mounted.
SAFETY
• Immediately disconnect the system if the installation or the floating platform exhibits deviation from standard operating conditions.
• In the event of the floating platform being submerged, disconnect the DC connection at the inverter immediately. Do not aempt to salvage panels
when sunlight is present.
NOTE
For all installations on water platforms, first advise REC before the start of installation in case of any site specific instructions or constraints.
i
NOTE
Negative system grounding is required for REC solar panels installed on a floating platform.
i
NOTE
For installations with high avian activity, system cleaning may be required at more frequent intervals to reduce shading of panels caused by bird defecation.
i
Ref: PM-DSRev- A .
www.recgroup.com
Founded in , REC Group is an international pioneering solar energy company
dedicated to empowering consumers with clean, aff ordable solar power. As Solar’s
Most Trusted, REC is commi ed to high quality, innovation, and a low carbon
footprint in the solar materials and solar panels it manufactures. Headquartered in
Norway with operational headquarters in Singapore, REC also has regional hubs in
North America, Europe, and Asia-Pacifi c.
IEC :, IEC :, UL
IEC PID
IEC Salt Mist
IEC Ammonia Resistance
UL Fire Type Class
IEC Dynamic Mechanical Load
IEC : Hailstone (mm)
ISO :, ISO :, OHSAS : , IEC
Specifications subject to change without notice.Ref: PM-DSRev- A .
WARRANTY
GENERAL DATA
Cell type: half-cut mono c-Si n-type cells
strings of cells in series
Glass: .” (. mm) solar glass with
anti-refl ection surface treatment
Backsheet: Highly resistant polymeric
construction (black)
Frame: Anodized aluminum (black)
with silver support bars
Junction box: -part, bypass diodes, IP rated
in accordance with IEC
Cable: AWG ( mm PV wire, + ” (. m + . m)
in accordance with EN
Connectors: Stäubli MC PVKBT/KST, AWG( mm)
in accordance with IEC
IP only when connected
Origin: Made in Singapore
LOW LIGHT BEHAVIOUR
TEMPERATURE RATINGS
*
MAXIMUM RATINGS
MECHANICAL DATA
Dimensions: . x . x . in x x mm)
Area: . s q . m)
Weight: . lbs (. kg)
Operational temperature: ... +°C
Maximum system voltage: V
Maximum test load (front): + Pa ( psf)
*
Maximum test load (rear): - Pa (. psf)
*
Max series fuse rating: A
Max reverse current: A
*
See installation manual for mounting instructions.
Design load = Test load / . safety factor)
ELECTRICAL DATA STC
Product code
*
: RECxxxNP Black
Nominal Power - P
MAX
(Wp)
Wa Class Sorting - (W) /+ /+ /+ /+
Nominal Power Voltage - V
MPP
(V) . . . .
Nominal Power Current - I
MPP
(A) . . . .
Open Circuit Voltage - V
OC
(V) . . . .
Short Circuit Current - I
SC
(A) . . . .
Panel Effi ciency () . . . .
Values at standard test conditions (STC: air mass AM ., irradiance W/m, temperature °C), based on a production spread with a
tolerance of P
MAX
, V
OC
& I
SC
± within one wa class. * Where xxx indicates the nominal power class (P
MAX
) at STC above.
ELECTRICAL DATA NOCT
Product code
*
: RECxxxNP Black
Nominal Power - P
MAX
(Wp)
Nominal Power Voltage - V
MPP
(V) . . . .
Nominal Power Current - I
MPP
(A) . . . .
Open Circuit Voltage - V
OC
(V) . . . .
Short Circuit Current - I
SC
(A) . . . .
Nominal operating cell temperature (NOCT: air mass AM ., irradiance W/m, temperature °C, windspeed m/s).
* Where xxx indicates the nominal power class (P
MAX
) at STC above.
CERTIFICATIONS
Nominal Operating Cell Temperature: .°C (±°C)
Temperature coeffi cient of P
MAX
: . /°C
Temperature coeffi cient of V
OC
: . /°C
Temperature coeffi cient of I
SC
: . /°C
*
The temperature coeffi cients stated are linear values
Rel. Effi ciency ()
REC N-PEAK 2 BLACK SERIES
100 200 300 400 500 600 700 800 900 1000
85
90
95
100
105
Irradiance (W/m)
Typical low irradiance performance of module at STC.
Measurements in mm [in]
Standard REC ProTrust
Installed by an REC
Certifi ed Solar
Professional
No Yes Yes
System size any ≤ kW kW
Product Warranty (yrs)
Power Warranty (yrs)
Labor Warranty (yrs)
Power in Year
Annual Degradation . . .
Power in Year
See warranty documents for details. Some conditions apply.
GR
GR
GR
GR
11±0.2
[0.43 ±0.1]
6.6±0.2 [0.26 ±0.1]
20.5±0.5
[0.8 ±0.02]
GR
638 ±1 [25.1 ±0.04]
30 [1.2]
22.5 [0.9]
28 [1.1]
1755±2.5 [69.10 ±0.1]
845 [33.27]
156 [6.14]
156 [6.14]
455 [17.91]
999 [39.33]
1100 [43.3]
5.5±0.2
[0.22±0.01]
1200 [47.2]
1040±2.5 [40.94 ±0.1]
17 [0.7]
45 [1.8]