Panel Install Manual

Table Of Contents
REC Installation Manual - REC Panels - UL 6
Rev L  . Ref: PMIM
PANEL INSTALLATION
REC solar panels are designed for capturing solar radiation and can be installed where they conform to all local structural regulations. If installing REC
solar panels in overhead or vertical constructions, the installer must ensure that all local building codes and regulations specific to such installations are
correctly followed. There are different options for securing REC solar panels depending on the design of the array. Mounting hardware is not supplied
by REC. Ensure the mounting structure can withstand anticipated wind and snow loads. Follow the mounting hardware manufacturer’s instructions and
recommendations at all times.
SECURING OF PANELS
A typical installation of solar panels will be carried out with suitable rails and clamps. Other types of panel support, e.g., plates, must meet the same
specifications. Such installations have been found to be in compliance with IEC  & IEC  requirements for the maximum stated test loads
which can be found for each individual panel type in the Panel Characteristics section at the end of this manual. Site-specific factors such as high wind
or snow levels must be taken into consideration to ensure this limit is not exceeded.
When installing on mounting rails, ensure they run underneath the panel and provide support to the frame. The positioning of the rail must ensure that
the minimum clamp grip length (fig. ) and the central point of the fixation, e.g., the bolt, is fully within the required clamping zone as indicated on the
following pages.
REC modules must be secured with a torque as shown in the table below (fig. ). Clamp installation must be carried out according to the
manufacturer’s instructions, including specific hardware and torque requirements. Ensure the clamps used are suitable for the planned installation
and expected system design loads.
The grip area must not extend onto the panel glass and/or cause cell shading,
Avoid the application of excessive pressure to prevent frame deformation,
The panel must be secured, e.g., clamped, at least once in each of the four marked zones shown below (fig. ).
Min. grip length
Grip depth
NOTE
In areas of snow build-up, panels can be subjected to forces in excess of the stated limit even when snow depth does not appear extreme, potentially
causing damage to the panel. If the installation may be affected by this, further panel support is recommended, especially on the lower row of panels.
In the case of any questions regarding mounting systems, or if the mounting system to be used does not match any of the instructions shown in
this installation manual, please contact REC for further support.
i
Specifications Length
Grip depth . - . in ( -  mm)
Min. grip length . in ( mm)
Torque
 -  Nm
(- lbf/in)
NOTE
Panels must be installed so that the cells are not shaded as this will drastically reduce electrical output. If partial shading is inevitable at certain times
of the day or year, it must be kept to an absolute minimum. Remove any labels or stickers that may be on the front of the panels and ensure no residue
is le on the glass.
i
NOTE
Common hardware items such as nuts, bolts, star washers, lock washers and the like have not been evaluated for electrical conductivity or for use as
grounding devices and should be used only for maintaining mechanical connections and holding electrical grounding devices in the proper position for
electrical conductivity. Such devices, where supplied with the panel and evaluated through the requirements in IEC  & UL , may be used
for grounding connections in accordance with the instructions provided with the panel.
i
CAUTION
There must be a minimum clearance gap between the uppermost part of the installation surface (e.g., rooop) and the lowest part of the panel (i.e.,
underside of panel frame) to avoid any damage to the panel and to ensure sufficient airflow for cooling, helping to improve performance.
Minimum clearance gap -cell format REC solar panels:  mm
Minimum clearance gap -cell format REC solar panels:  mm
The surface below the panels must be kept clear of any objects that may cause damage to the panel.
Fig. : Clamp specifications
1
2
43
Fig. : Panel quarter divisions