User guide
BACnet/IP Server Object Configuration – Binary Objects
Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACnet/IP Server
Configuration page to access the Object Configuration page for this device.
When in Auto-Server Mode, these fields are not configurable.
Follow these steps to configure Binary Input or Outputs in Manual Mode.
1) Select Binary Input or Binary Output from the upper left dropdown menu.
2) Select a Group to use.
These group names are defined in this under BACnet Advanced configuration.
3) Enter a Name to identify this object on the network.
The combination of Group and Name should be unique for each point in the gateway.