BACnet/IP Server Object Configuration – Analog Objects
Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACnet/IP Server
Configuration page to access the Object Configuration page.
When in Auto-Server Mode, these fields are not configurable.
Follow these steps to customize Analog Inputs or Outputs in Manual Mode.
1) Select Analog Input or Analog Output from the upper left dropdown menu.
2) Select a Group to use.
These group names are defined in this under BACnet Advanced configuration.
3) Enter a Name to identify this object on the network.
The combination of Group and Name should be unique for each point in the gateway.
4) Select the Unit Category corresponding to the units you want this object to be identified with
(optional). Then select the Unit from the dropdown menu.
5) Set the COV (Change Of Value) for this object.
If the BACnet/IP Client issues a COV-Subscription, the gateway will issue a COV
Notification when the Present-Value changes by more than the given COV-Value. This
value shift can be in a positive or negative direction.