BACnet/IP Server Configuration
Click the BACnet/IP Server button to access the primary configuration page for this device.
1) Enter a Device Label. This is an internal device alias used during data mapping.
2) Enter the decimal value of the UDP Port that the gateway will communicate on (Default is 47808
(0xBAC0)).
3) Enter a unique Instance identifier for the gateway. This Instance must be unique on the
BACnet/IP network.
4) Inactivity Timeout: Enter the amount of time, in milliseconds, the gateway should wait before a
timeout state is declared. If the BACnet/IP Client does not initiate communication within this
time frame the BACnet/IP LED will flash red and the timeout counter will increment. Enter 0 to
disable this feature.
5) Enter a Name, Description and Location for the gateway. These are used to identify the gateway
on the BACnet/IP network.
6) Bit Pack: Select the formatting of the Binary Input/Output. Automap will use this packing size to
map binary objects to/from the other protocol.