User guide
Specifications A–9
Hitachi Unified Storage VM Block Module Hardware User Guide
Earthquake
resistance (m/s2)
Up to 2.5
10
--
Shock -
78.4 m/s
2
, 15 ms Horizontal
8
Incline Impact 1.22 m/s
Vertical:
Rotational Edge 0.15 m
9
Acoustic Level
DBS
DBL
DBX
DBF
60dB
60dB
62dB
60dB
55dB
55dB
57dB
55dB
n/a
Dust Less than 0.15mg per
cubic meter of air
--
Altitude -60 m to 3,000 m -60 m to 12,000 m
Notes:
1. Environmental specification for operation should be met before the storage system is powered on.
Maximum temperature of 90°F / 32°C should be strictly met at air system air inlet.
2. Recommended temperature range is 21 to 24°C
3. Non-operating condition includes both packing and unpacking conditions unless otherwise
specified.
4. The system and components should be packed in factory packing for shipping and storing
5. No condensation in and around the drive should be observed under any conditions. No
condensation in and around the drive should be observed under any conditions.
6. The above specifications of vibration are applied to all three axes
7. See ASTM D999-01 The Methods for Vibration Testing of Shipping Containers.
8. See ASTM D5277-92 Test Method for Performing Programmed Horizontal Impacts Using an Inclined
Impact Tester.
9. See ASTM D6055-96 Test Methods for Mechanical Handling of Unitized Loads and Large Shipping
Cases and Crates.
10. Time is 5 seconds or less in case of the testing with device resonance point (6 to 7Hz.
Item Operating
1,2
Not Operating
3
Shipping and Storage
4