A–6 Specifications
Hitachi Unified Storage VM Block Module Hardware User Guide
Table A-5: HUS VM electrical specifications, three phase current
Table A-6: Power consumption, single phase current
Item Unit Specification
Power
requirements,
system operating
1
AC, three phase
2
208 V +5/-15%, 50/60 Hz
3
Maximum 41.4 KVA
Controller chassis
power supply
Input Current 3.81 A
Steady Current 1.91 A
Leakage Current 0.28 mA
Inrush current 1st (0-p) 25 A
2nd (0-p) 20A
1st (0-p) Time
(-25%: 150 ms
SFF drive box
power supply
Input Current 2.61 A
Steady Current 1.31 A
Leakage Current 1.75 mA
Inrush current 1st (0-p) 25 A
2nd (0-p) 20A
1st (0-p) Time
(-25%: 150 ms
Dense drive box
power supply
Input Current 4.03 A
Steady Current 2.02 A
Leakage Current 0.87 mA
Inrush current 1st (0-p) 30A
2nd (0-p) 30A
1st (0-p) Time
(-25%: 150 ms
Notes
1. 110/120 VAC system is not supported
2. See Table A-7: PDU plugs, circuit breakers, and receptacles on page A-7 for
information about poles and current.
3. The total power consumption of the system is the same whether it uses single
phase or three phase power. The difference is that each branch of the three phase
input power draws less current than the single phase conductors.
Configuration
1
Max Power Consumption
3, 5
Current per rack
R00 controller
4
R01 drive 1)
4
R02 drive 2)
4
Total Power