User guide

Site preparation 4–17
Hitachi Unified Storage VM Block Module Hardware User Guide
Operational requirements
The operational requirements for the HUS VM include:
LAN for Storage Navigator
Storage Navigator communicates with the HUS VM storage system over a
LAN to obtain system configuration and status information and send user
commands to the storage system. Storage Navigator serves as the
integrated interface for all resource manager components.
Cable length for host I/O modules
The following table lists the cable length requirements for the host I/O
modules in the HUS VM storage system.
Table 4-12: Maximum cable length (shortwave)
Figure 4-5: Service Clearances, single rack system
DataTransfer
Rate
OM1(62.5/125 f/m
multi-mode fiber)
OM2(50/125 f/m
multi-mode fiber)
OM3(50/125 f/m laser
optimizedmulti-mode fiber)
MB/s feet / meters feet / meters feet / meters
200 492.1 / 150 984.3 / 300 1640.4 / 500
400 229.7 / 70 492.1 / 150 1246.7 / 380
800 68.9 / 21 164 / 50 492.1 / 150