F.3.4 Definition of the parameter data set for a ‘Radio Slave’
The GSD file contains the following parameters (projecting via a master specific software):
Parameters (Display projecting tool) Configurable parameters Description
All inputs 0 Timeout_Mode
Hold old values
Defines how input data of the slave should behave, if a
NO_LINK-Timeout occurs.
Timeout NO_LINK-Diag Unsigned Integer:
Value in ms.
Values between 1000 ms
and 65536 ms are allowed.
Defines the timeout time to the polling radio master until
diagnose information is set on profibus.
Modem Guard Time
Recommended: 200ms
Unsigned Integer:
Value in ms.
Values between 0 ms and
65500 ms are allowed.
Defines the time which must keep before a new radio slave
could be selected.
Radio Slave Address Byte:
Values between 1 and 8
are allowed.
Defines the address of the Radio Slave module.
Timeout_Mode (Bool): This parameter defines, how the profibus input data of the profibus
slave should behave, if a NO_LINK-Timeout is detected. The selection „All inputs 0“ sets all
input data to zero, whereas the selection „Hold old values“ saves the last values in the register
area.
Timeout NO_LINK-Diag (Integer value in ms): Defines how long no data from the radio
master station can be received until a diagnose information (NO_LINK-Diag) is set onto the
profibus.
Modem Guard Time (Integer value in ms): Defines how long the radio slave module must
wait until it configures the address of the radio modem.
Radio Slave Address (Byte): Defines the own address of the Radio Slave which is set on
startup of Profibus communication via serial to the radio modem.
Important note:
These defined settings (project data) are sent through the profibus master during
network startup.