F.3.2 Definition of the configuration data set for a ‘Radio Master’
The configuration data set defines the number of data bytes, which are cyclically transmitted
via the Profibus.
This number of bytes is fixed for the respective used ‘Radio Master’-module. It is possible to
select one of max. eight different available ‘Radio Master’ modules. All modules have the same
parameter data set, but different amount of input/output data.
For each ‘Radio Slave’ there were 30 data bytes needed.
List for several Radio Master:
Radio Master (1 Radio Slave): maximum of data input: 30 bytes
Radio Master (2 Radio Slave): maximum of data input: 60 bytes
Radio Master (3 Radio Slave): maximum of data input: 90 bytes
Radio Master (4 Radio Slave): maximum of data input: 120 bytes
Radio Master (8 Radio Slave): maximum of data input: 240 bytes
The ‘Radio Master’-module must selected for the respective scenario the Smart_DP for Radio
Modem Series – module is used for.
Important note:
These defined settings (configuration data set) are sent by the Profibus master during
network startup.